FIRE-RATED SINGLE-VALVE
OUTLET PLATE
DESIGN SPECIFICATION
1. WALL CONSTRUCTION
a. Wood or metal stud construction
b. 16" on-center stud construction.
c. Double-layer ⅝" gypsum construction with 2-hour fire rating.
Single-layer ⅝" gypsum construction with 1-hour fire rating.
d. Plates cannot be installed back to back.
Fire-Rated escutcheon available separately (Item No. 699RF)
2. PIPE/PLATE SUPPORT
a. Maximum 2 plates installed in a 16" O.C. stud cavity secured to brackets when
centered or direct mounted to stud.
b. ProPlate
Fire-rated bracket (back side of plate)
c. Common flat brackets.
3. PIPE MATERIAL
a. Metallic or plastic water supply pipe.
b. Supply lines to be installed using ordinary methods.
4. FIRE-RATED RESINS
Sioux Chief fire-rated ProPlate uses fire-rated resin.
NOTE: Gaps up to ½" around plate can be sealed with drywall plaster.
Larger gaps require firestop sealant applied to opening spanning entire drywall depth
THE FIRE-RATED PROPLATE IS CERTIFIED BY INTERTEK
TO THE FOLLOWING FIRE RATING STANDARDS:
ASTM E-814 | UL1479
CAN/ULC S115
1hr (F), 56min (T) for 1-hour design
Design No: SCMC/PF 60-01
2hrs (F), 2hrs (T) for 2-hour design
Design No: SCMC/PF-120-1
Sioux Chief Manufacturing Company
FIGURE 1
UL D. #U341
1c
FINISH INSTALLATION
|
P: 1.800.821.3944
|
F: 1.800.758.5950
3a
2b
2c
3a
Escutcheon
|
www.siouxchief.com
1a/b
6-21