SYMPTOM
DISPLAY IS
INACCURATE
DISPLAY IS
FADED OR
BLANK
NORMAL FLOW
RATE BUT
DISPLAY DOES
NOT SHOW
COUNT
REDUCED FLOW
RATE AND
DISPLAY DOES
NOT SHOW
COUNT
7
TROUBLESHOOTING
PROBABLE CAUSE
Meter operated below
minimum flow rate.
Meter partially clogged with
debris.
Sealant material wrapped
around meter rotor.
Batteries weak, dead, or not
connected.
Computer defective.
Rotor stuck or damaged.
Sealant material wrapped
around rotor.
Computer defective.
Meter clogged with debris.
Below minimum flow rate.
CORRECTIVE ACTION
Increase flow rate.
Remove meter. Clean
carefully. Make sure rotor
spins freely and water supply
is free of debris.
If applicable, remove rotor.
Make sure rotor spins freely
and water supply is free of
debris. .
Check and replace batteries.
Contact the factory.
Remove meter. Make sure
rotor spins freely.
Remove meter. Make sure
rotor spins freely.
Contact the factory.
Remove meter. Clean
carefully. Make sure rotor
spins freely and water supply
is free of debris.
Increase flow.