Technical data / Caractéristiques techniques / Datos técnicos
Electrical
supply inlet
1
RLA
(A)
230/1/60
8.9
SRL- - 250
230/3/60
7.1
460/3/60
3.3
230/3/60
7.1
SRL 325
SRL- - 325
460/3/60
3.3
230/3/60
7.9
SRL- - 400
SRL 400
460/3/60
3.9
230/3/60
10
SRL- - 500
SRL 500
460/3/60
5
230/3/60
13.9
SRL- - 700
SRL 700
460/3/60
6.4
230/3/60
13.9
SRL- - 800
SRL 800
460/3/60
6.4
SRL- - 1000
460/3/60
7.9
Calibration values
Hot gas valve
62.4 --- 66.7 PSIg
SRL- - 250
4.3 --- 4.6 barg
66.7 --- 69.6 PSIg
SRL- - 325 --- SRL- - 1000
4.6 --- 4.8 barg
Compressor
Fan motor
MC1 (Ac/Wc)
3
EV1 (Ac)
LRA
RLA
(A)
(A)
51
0.78
38
0.78
20
0.78
38
0.61
20
0.61
45
0.61
23
0.61
63
0.61
31
0.61
88
2.2
44
1.25
88
2.2
44
1.25
50
1.25
Fan pressure switch
9
HGV
12 PV
ON: 261 PSIg
OFF: 203 PSIg
ON: 18 barg
OFF: 14 barg
Minimum
circuit ampacity
MCA (Ac)
MCA (Wc)
(HP)
(HP)
(A)
(A)
(A)
(A)
0.19
11.7
---
0.19
9.41
---
0.19
4.63
---
0.59
8.90
---
0.59
4.84
---
0.59
9.88
---
0.59
5.62
---
0.59
12.5
---
0.59
7.00
---
1.07
19.6
17.4
1.07
9.3
8
1.07
19.6
17.4
1.07
9.30
8.00
1.07
11.1
9.90
High pressure switch
15 HP
406 PSIg
g
g
28 barg
Maximum
protection device rating
HACR (Ac)
HACR (Wc)
(A)
(A)
(A)
(A)
15
---
15
---
10
---
10
---
6
---
15
---
10
---
15
---
10
---
20
20
15
15
20
20
15
15
15
15
Low pressure switch
Water pressostatic valve
6
LP
21.8 --- 36.3 PSIg
g
1.5 --- 2.5 barg
SRL- - 250 --- SRL- - 1000 (60Hz)
Minimum section
validated cable for
validated cable for
eletrical connection
12AWG
12AWG
14AWG
12AWG
14AWG
12AWG
14AWG
12AWG
14AWG
12AWG
12AWG
12AWG
12AWG
12AWG
22 WPV
232 PSIg
g
16 barg
23