English
Z
7
Troubleshooting
CP
compressor
Compressor
thermal protec-
noisy
tion alarm
Compressor
Condenser
components
dirty or
deteriorated
obstructed
no
yes
no
Repair or
Compressor
replace
yes
winding
compressor
with partial
Z
loss of
insulation
no
FAULT
Lt Low evaporation temperature alarm
Ld Low dew point alarm.
Low
yes
cooling
air
temperature
no
Fan
yes
always
working
(PV pressure
switch fault)
no
Hot gas
yes
valve
not calibrated
no
yes
Clean
condenser
yes
Replace
the coil
Z
CAUSE
REMEDY
LP Low
pressure
alarm
Increase
LP
yes
pressure
cooling air
Low pressure
temperature
switch fault
no
Replace
pressure switch
Z
(air flow, inlet temperature)
no
Calibrate
valve
Z
Fan
yes
pressure switch
(PV) not set
no
Liquid line
Low
yes
solenoid valve
current
closed
absorption
no
no
Request external assistance
Ht
High
High
dew point
temperature
warning
alarm
Cooling
Replace
yes
air
high
switch
temperature
Z
no
Excessive thermal load
yes
no
Replace
Condenser
yes
pressure switch
dirty or
Z
obstructed
no
No
Low
refrigerant.
yes
current
Recharge
absorption
Z
no
6
SRL- - 250 --- SRL- - 1000 (60Hz)
HP
high pressure
alarm
Cooling
Decrease
yes
air
cooling air
high
temperature
temperature
no
Decrease
Excessive
yes
compressed
thermal load
air quantity
(inlet air flow,
temperature
temperature)
no
Condenser
yes
Clean
dirty or
condenser
obstructed
no
Fan
Replace
yes
does not turn
pressure switch
(PV pressure
Z
switch fault)
no
Fan
Replace fan
yes
Z
fault
no