Auxiliary Switches
a or
Notes on mounting and wiring Auxiliary Switches for UL/CSA labeled models:
– M22-K(10)(01) have screw terminals. M22-CK(10)(01) have clamp terminals.
– Switch modules are snapped into place at the locations shown in the diagrams that follow.
– Switches will function as either „standard" or „trip/alarm" contacts depending on their mounting location.
– Location „HIN" refers to standard operation. Location „HIA" refers to „trip/alarm" operation.
– Follow the numbering and wiring scheme provided above depending on the contact location and function. (N.O. or N.C.)
– Permissible contact configuration: 1 HIA and/or 2 HIN.
Note:
After mounting of the M22... switch is complete, check off the appropriate box on the auxiliary switch
label provided on the side of the breaker or switch.
M22-K11
HIA
M22-CK20
4.13
4.11
M22-CK02
4.14
4.12
① or
2
I r
6 x I r
t
r
I sd
I >
t sd
I >
HIN
4.13
4.11
1.13
①
①
4.14
4.12
1.14
4.13
4.23
4.11
①
①
4.14
4.24
4.12
I
[A], t
[s], I
2
r
r
Electronic Trip Circuit Breaker Adjustable settings
(I
= Max. current rating)
n
I
= Adjustable current setting (0.5 - 1.0 x I
r
t
= Adjustable Long Time Pick-up Delay (2 - 20 sec.) factory set at 10 seconds.
r
I
= Adjustable Short Time Pick-up (2 - 10 x I
sd
t
= Short Time Pick-up Delay (0 - 1000 ms) factory set at 0 ms.
sd
t
r = 20 s
Note: Instantaneous Pick-up fixed at 12 x I
t
r = 2 s
HIN
1.11
1.23
1.21
①
1.12
1.24
1.22
HIN
1.13
4.21
...
1.14
4.22
M22-CK11
①
M22-CK20
①
M22-CK02
[A], t
[ms]
sd
sd
Z 2
) for Long Time Pick-up.
n
) factory set at 6 x I
r
.
n
-NA
-CNA
(UL/CSA)
U
(V)
e
600 AC
250 DC
Pilot Duty Ratings:
B 600, Q 300
Above 300 V AC
Same polarity
IEC
I
= I
th
e
U
(V)
e
AC-15
115
230
400
500
DC-13
24
42
60
110
220
1.11
1.41
1.43
...
AC-15
1.12
1.42
1.44
DC-13
.
r
I
= I
th
e
I
(A)
e
5 A
1 A
I
(A)
e
4
4
2
1
3
1.7
1.2
0.6
0.3
IEC
I
= I
th
e
U
(V)
I
(A)
e
e
115
4
230
4
24
3
42
1
60
0.8
110
0.5
220
0.2
7/10