Day/Night controller
Output signals
The polarity of the motor wires depends on whether the motor is left or right
hand mounted. During an UP command, motor output A goes to the positive
signal and motor output B goes to the negative signal. The motors should be
connected accordingly.
5.2
Setting the runtime
DIP switches DIP 1, DIP 2, DIP 3 and DIP 4 set the time period that the motors run
for on receipt of a command. The preset minimum time is 5 seconds. This can be
increased in increments as shown in the following table up to a maximum of
80 seconds.
Runtime
5 s
10 s
15 s
20 s
25 s
30 s
35 s
40 s
45 s
50 s
55 s
60 s
65 s
70 s
75 s
80 s
5.3

Setting the operating mode

There are two operating modes: RFB for roof blinds and DNC for window blinds.
Upon receiving a command, the output relays energize in a set sequence to con-
trol the motors fitted to the blinds.
Any subsequent commands received during runtime are treated as a stop com-
mand. Since the motors may have already stopped on their own limit switches,
this can cause confusion to the operator. Therefore, the runtime has to be as
close as possible to the actual runtime of the blind with an additional tolerance
due to fluctuations in motor speed.
EN
DIP 1
DIP 2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Installation
DIP 3
DIP 4
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
7