Descargar Imprimir esta página

Required Tools; Emc-Compliant Installation - Danfoss VLT D1h Guia De Instalacion

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 34
VLT® Frequency Converters, 90–400 kW
Installation Guide

1.5 Required Tools

Lifting aid
Tape measure
Drill with assorted bits
Screwdrivers (Torx, Phillips, slotted)
Wrench with 7–17 mm sockets
Socket extensions
Sheet metal punch and/or pliers
Wire crimper
1.6 Verifying the Shipment and the Contents
Make sure that the items supplied and the information on the nameplate match the order. The nameplate is on the exterior of the
drive.
The type code is used in the fuse table. Write down the type code (T/C) and serial number (S/N) for future reference.
1
2
3
4
5
Illustration 1: Example of the Type Code on the Nameplate
1
Type code
2
Part number and serial number
3
Power rating

1.7 EMC-compliant Installation

For more information, refer to the product-specific operating guide.
Use shielded cables for motor (unshielded cables in metal conduit are acceptable), brake, DC, and control wiring.
Ensure that motor, brake, and DC cables are as short as possible to reduce the interference level from the entire system. Provide
a minimum space of 200 mm (7.9 in) between mains input, motor cables, and control cables.
Convey the currents back to the drive using a metal mounting plate. Ensure good electrical contact from the mounting plate
through the mounting screws to the metal frame of the enclosure.
6 | Danfoss A/S © 2022.08
N O T I C E
6
4
Input/output voltage, frequency, and current
5
Enclosure protection rating
6
Enclosure size
Instructions
AN41701949085201-000101 / 130R1260

Publicidad

loading