CONTROLS
10
A low voltage control must be used with the Santa Fe Ultra155/205.
2. Terminal Block Control Operation
COM
FAN
24V
DEHU
Float
Between the COM lead and the 24V TERMINAL is a 40VA transformer. This low voltage power source powers
the relay coils which control the fan and compressors. This 24VAC transformer can also be used to power
HVAC accessories external to the dehumidifier.
Compressor ON/Fan On
Compressor OFF/Fan On
Power HVAC Accessory
NOTE: 18 gauge wire needed between the Santa Fe Ultra155/205 dehumidifier and the external control.
18
Santa Fe ULTRA155/205 Installation & Operation Instructions
24VAC Power Transformer Neutral Side
Fan Control
Transformer High Side
Dehumidification (Fan and Compressor) Control
External low voltage float switch or water sensor
(two terminals) Use normally closed switch
Make contact between 24V and DEHU terminals
Make contact between 24V and FAN terminals
Connect the accessory to the DMPR and 24V terminals
Santa-Fe-Products.com | 800.533.7533