WARNING
Danger from voltage/current!
Only perform assembly and disassembly work when the device is de-energized.
Install products with degree of protection IP65/67 according to IEC 60529 weatherproof and stationary.
WARNING
Safety functional extra low voltage
The product must be operated with safety functional extra low voltage (SELV, PELV). You can find more information on
safety functional extra low voltage in the documentation (https://support.industry.siemens.com/cs/ww/en/view/109781058)
of the fail-safe I/O and in the data sheets of the power supplies to be used.
Use a power supply unit with output voltage that does not exceed 35 V DC even in the event of a fault.
Follow the notes and warnings in the respective manual.
Electromagnetic Compatibility
The I/O system is intended for operation in the EMC environment class Industry.
Ensure an EMC-compliant design of your automation system as described in the documentation
(https://support.industry.siemens.com/cs/ww/en/view/109781058) for the I/O system.
NOTICE
Interference emission / Interference immunity
The operation of the I/O system can cause radio interference in residential areas.
If higher EMI is expected at the place of use than is intended for the industrial area according to EN61000-6-2, additional
measures are required (e.g. ESD, overvoltage protection).
ATEX-/UKEX device intended for use in hazardous area
If the product is intended for use in a potentially explosive atmosphere (gas/air or gas/dust mixture), observe the special
information in the documentation (https://support.industry.siemens.com/cs/ww/en/view/109781058). The intended use (e.g.
ATEX zone, degree of protection, temperature class) is indicated on the product (in the declaration of conformity and usually
also on the nameplate).
Note
As a rule, country-specific requirements for the operator also apply when a product is used in a potentially explosive
atmosphere (e.g. Directive 1999/92/EC for the EU).
Cleaning
When wired, the product complies with degree of protection IP65/IP67 and does not require any cleaning.
If you do have to clean the product, then use a dry or damp cloth. Take care to comply with the conditions of degree of
protection IP65/IP67 when cleaning with liquids.
Maintenance and repair
The product is maintenance-free. Repairs to the product may only be carried out by the manufacturer.
Recycling and disposal
For environmentally sustainable recycling and disposal of your electronic waste, contact a company certified for the disposal
of electronic waste. Dispose of the product in accordance with the applicable regulations in your country.
Accessories
You can find information on the approved accessories in the documentation
(https://support.industry.siemens.com/cs/ww/en/view/109781058).
8
ET 200eco PN/ET 200eco PN M12-L distributed I/O system
A5E51784772-AA, 03/2022