Descargar Imprimir esta página

LEGRAND Wattstopper LMDC-100 Instrucciones página 4

Ocultar thumbs Ver también para Wattstopper LMDC-100:

Publicidad

Idiomas disponibles

Idiomas disponibles

By default, the sensor will be bound to all loads within the DLM Local network. You can unbind or bind specific loads load using Push 'n
Learn (PnL).
You can enter PnL Mode from any DLM device in the room. To enter PnL mode, Press and hold on the Configuration button on any
device for 3 seconds. The Red LED begins blinking rapidly (2x/second) on all communicating devices connected to the DLM Local
Network. These Red LEDs continue to blink until you exit Push n' Learn mode.
• All loads in the room except load #1 turn OFF immediately after entering Push n' Learn.
• The blue status LED is solid ON at every device bound to the load when the load is ON. To unbind the load from the sensor, press
the Load button. The Blue LED on the sensor will turn Off, when it is not bound to the load. If unbound, press Load again to rebind.
• To switch to load 2, press and release the Config button. Each time, you press the Config button it will step through each load in the
room and wrap around back to load 1 after the highest numbered load. You can then repeat the process to bind unbind or bind the
senor to that load.
To Exit PnL, press and hold the Config button 3 seconds, until the red LED turns Off.
Be sure to EXIT PnL when you are finished making load changes. If you leave the network in PnL, undesired bindings and load
parameter setting changes may occur.
ON Mode Operation*
Blink Warning
* Auto-Off is enabled according to the sensor Time Delay when a sensor is bound to the load, regardless of whether the load was
turned on automatically with occupancy or manually using a switch.
** Reference room/plug load controller documentation for maximum load limits.
Loads do not operate as expected.
LEDs don't light.
The wrong lights are
controlled.
LEDs turn ON and OFF
but load doesn't switch.
MAKING PUSH N' LEARN CHANGES ON THE SENSOR
DEFAULT SENSOR BEHAVIOR
Load 1
MANUAL-ON if switch is connected.
AUTO-ON
AUTO-ON if no switch.
OFF
OFF
TROUBLESHOOTING
1. Check to see that the the sensor is connected to the DLM local Network.
2. Check for 24VDC input to the sensor: Plug in a different DLM device at the sensor location. If the
device does not power up, 24VDC is not present.
• Check the high voltage connections to the room controller.
• If high voltage connections are good and high voltage is present, recheck DLM local Network
connections between the sensor and the room controller.
1. Configure the sensor to control the desired lights using the Push n' Learn adjustment procedure.
1. Make sure device is not in PnL.
2. Check load connections to room controller.
Loads 2 or higher**
CAUTION: TO CONNECT A COMPUTER TO THE DLM LOCAL NETWORK
USE THE LMCI-100. NEVER CONNECT THE DLM LOCAL NETWORK
TO AN ETHERNET PORT – IT MAY DAMAGE COMPUTERS AND OTHER
CONNECTED EQUIPMENT.
4
Plug Load
AUTO-ON
OFF

Publicidad

loading