Setting the End of Line Jumpers
When two or more modules are connected together through the SBI, you must set the end of line (EOL)
jumpers on the electronic card according to the position of the module in the series.
1. Locate the last module of the communication loop, and set the EOL to Yes.
2. Set the EOL jumpers on all other modules to No.
Assigning an Identification Number
1. Once the connections have been made, close the enclosure and apply power to the unit.
The display shows ID 55 which is the default device identification (ID) number.
2. Press the Gear button twice to change the device id number.
The number 2 flashes on the display.
3. Press the button as many times as required to set the ID number.
4. To record the ID number in memory, press and hold the button for 5 seconds.
The ID number stops flashing.
Table 1-1 Display codes
Lz ##
Gz ##
Er
895-00397 TP-800
Chapitre 1: Connections and Configuration
Local zone ## has an alarm
System zone ## has an alarm
Error - contact your dealer. A trouble on a TP800
zone