PSU67-1P-1M-2M5-24150-IOL-F
EN
Quick Start Guide
If capacitors with a capacitance >20 mF are connected to one output, this
output might switch off after turning the unit or the output on or connect-
ing the load.
Operating
CAUTION
Hot surfaces
Burn risk
Do not touch the housing during operation or shortly after power-off.
The green status LED indicates that the output voltage is above 90 % of the
set output voltage and that no output has been switched off due to overcur-
rent or overtemperature.
IO-Link interface
The device can be parameterized via IO-Link using the associated IODD. In
addition, device-internal measurement data and diagnostics are made avail-
able via IO-Link. The IODD programming software can be downloaded for
free from www.turck.com.
LED bar and push-buttons
The green Status LED reports an output above 90 % of the set output volt-
age.
■
Monitoring mode (normal operation):
Actual output power = percentage of 300 W (100 % = 300 W)
For values above 100 %, the LEDs flash orange. By pressing the up and down
keys, the output current of the respective output is displayed as a percent-
age of the set tripping current. The orange LEDs OUT1...OUT4 indicate the
selected output.
■
Configuration mode
Button [Voltage Set]
Hold for 3 s Configuration mode, all LEDs flash shortly
Start mode: "Set output voltage": The output voltage is set for all outputs.
All orange LEDs are off.
Hold for 3 s,
Mode "Set tripping current": The tripping current (s. fig. 4) is set
press 1×
separately for each output. The orange LEDs OUT1...OUT4 indicate the
selected output.
Hold for 3 s,
Select other output, n = no. of the output
press n ×
(only for "Set tripping current")
Buttons [] []
Set value
The set value for output voltage or tripping current is indicated via the
LED bar. The setting becomes effective immediately.
After 15 s without pressing the buttons, the LED bar switches back to normal
operation.
Hans Turck GmbH & Co. KG | Witzlebenstraße 7, 45472 Mülheim an der Ruhr, Germany | Tel. +49 208 4952-0 | Fax +49 208 4952-264 | more@turck.com | www.turck.com
Deactivating outputs
Press the button at the output channel (OUT1...OUT4) for at least 1 s to
activate or deactivate the output manually.
Maintenance
Clean the devices at regular intervals with a damp cloth.
Repair
The device must not be repaired by the user. Take defective devices out of
operation. Observe our return acceptance conditions when returning the
device to Turck.
Disposal
The devices must be disposed of correctly and must not be included
in normal household garbage.
Technical data
All values are typical figures specified at an input voltage of 100 VDC/230 VAC, 50 Hz,
24 VDC, 300 W output load, 25 °C ambient temperature and after a 5 minutes run-in
time unless specified otherwise.
Device
Type designation
PSU67-1P-1M-2M5-24150-IOL-F
Order number
100028304
Outputs
Output voltage
24 VDC (PELV), nominal value
Adjustment range
24...28 VDC
Output power, continuous at ambient temperature:
– at 45 °C
360 W
– at 55 °C
300 W
– at 70 °C
150 W
Output power, short-term, up to 5 s, at ambient temperature:
– up to 55 °C, input current ≥ 100 VAC
600 W
– at 70 °C
300 W
Linear derating between +45 °C and +70 °C (s. fig. 5)
Output currents
Up to 10 A, settable per output
Input
Input voltage AC
100...240 V -15/+10 %
Mains frequency
50 Hz/60 Hz ±6 %
⑤
P
/W
Out
600
360
300
150
0
-25
0
+45
Wiring diagrams
PE
2
1 = PE
2 = L
3 = N
1
3
2
Input 7/8" (XD1)
Output 7/8" (XD2, XD3)
1 = 24 VDC
1
2 = n.c.
4
2
3 = GND
5
4 = C/Q (IO-Link)
3
5 = n.c.
IO-Link M12 (X0)
Input current AC
4/1.7 A at 100/230 VAC
Power factor
0.99/0.97 at 100/230 VAC
Input inrush current (at 25 °C)
2.6/6 A peak at 100/230 VAC
Input voltage DC
110...300 V ±20%
Input current DC
3.6/1.3 A at 110/300 VDC
Efficiency
Efficiency
93.4/95 % at 100/230 VAC
Losses
20.8/23.0 W at 100/230 VAC
Hold-up time
33/33 ms at 100/230 VAC
Ambient conditions
Temperature range
-25...+70 °C
Max. operating temperature
+70 °C, measured 2 cm below the device
Relative humidity
5...95 %
Housing
Dimensions (l × w × h)
183 × 182 × 59 mm, without connectors
Weight
1200 g/2.7 lb
Degree of protection
IP65/IP67, only with correct mounting of
(according to IEC 60529)
all mating connectors
Protection against electrical, mechanical
and fire hazards
© Hans Turck GmbH & Co. KG | 100034421 2022-10
A: continuous
B: short term (max. 5 s)
B
A
+55
+70
T/°C
3
1 = GND (V2)
4
2 = GND (V1)
3 = FE
4 = 24VDC (V1)
5
5 = 24VDC (V2)