Penn | TC3B22 | Installation Guide Rev. A | Part No. 24-7664-03868 | Page 1 of 14 | January 20, 2022
TC3B22
Basic Defrost Controller European Installation Guide
Basic controller for refrigerated cabinets, with energy-saving strategies
Figure 1: UI
Figure 2: Dimensions, mm (in.)
Figure 3: Drilling template, mm (in.)
Figure 4: Electrical connection
ENGLISH
-
Controller for normal and low temperature units
-
Power supply for TC3B22N7x: 230 VAC
-
Cabinet probe and auxiliary probe with a negative temperature coefficient (NTC)
-
Door switch or multi-purpose input
-
Cooling or heating operation
1
MEASUREMENTS AND INSTALLATION
For the dimensions and drilling template, see Figure 2 and Figure 3. Fit the controller to a panel
with the snap-in brackets supplied.
INSTALLATION PRECAUTIONS
-
Ensure that the thickness of the panel is between 0.8 mm and 2.0 mm (1/32 and 1/16
in)
-
Ensure that the working conditions are within the limits stated in TECHNICAL
SPECIFICATIONS.
-
Do not install the device close to heat sources, equipment with a strong magnetic field,
in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations or
shocks.
-
In compliance with safety regulations, install the device correctly to ensure adequate
protection from contact with electrical parts. Fix all protective parts in such a way so as
to need the aid of a tool to remove them.
2
ELECTRICAL CONNECTION
Important
- Use cables of an adequate wire gauge for the current running through them.
- To reduce any electromagnetic interference, connect the power cables as far away
as possible from the signal cables.
For the electrical connection diagram, see Figure 4.
Electrical connection diagram callouts
Callout
Description
A
Note: Maximum 10 A
B
Compressor
C
Evaporator fans, configurable
D
Door switch or multi-purpose
E
Cabinet
F
Auxiliary, configurable
G
Power supply for TC3B22N7x: 230 VAC
PRECAUTIONS FOR ELECTRICAL CONNECTION
If you use an electrical or pneumatic screwdriver, adjust the torque to a maximum of
-
0.5 N•m (4 in. lb).
If you move the device from a cold to a warm place, the humidity may cause
-
condensation to form inside. Wait an hour before you switch on the power.
Make sure that the supply voltage, electrical frequency, and power are within the set
-
limits. See TECHNICAL SPECIFICATIONS.
Disconnect the power supply before you do any type of maintenance.
-
Do not use the device as safety device.
-
For repairs and further information, contact the Penn sales network.
-
3
FIRST-TIME
1.
Follow the instructions in MEASUREMENTS AND INSTALLATION to install the controller.
2.
Power up the device as shown in ELECTRICAL CONNECTION and an internal test runs.
The test normally takes a few seconds. When it finishes the display switches off.
3.
Configure the device as shown in Table 6.1 in SETTINGS.
For recommended configuration parameters for first-time use, see the following table.
PAR.
DEF.
PARAMETER
SP
0.0
Setpoint
P2
0
Temperature unit of measurement
d1
0
Defrost type
Check that the remaining settings are appropriate; see CONFIGURATION PARAMETERS.
4.
Disconnect the device from the mains.
5.
Make the electrical connection as shown in ELECTRICAL CONNECTION without powering
up the device.
6.
Power up the device.
4
UI AND MAIN FUNCTIONS
For a figure of the UI, see Figure 1.
UI callouts
Callout
1
2
3
4
5
6
7
8
9
10
11
12
13
4.1
Switching the device on or off
1.
If the device is switched on, the display shows the P5 value, cabinet temperature by default. If
the display shows an alarm code, see ALARMS.
LED
ON
Compressor on
Defrost or pre-dripping
active
Evaporator fan on
AUX
- Alarm active
- Cabinet light on by
key
- If device on, energy
saving active
- If device off, low
consumption active
°C/°F View temperature
Device off
If 30 s have elapse and you do not press the keys, the display shows the "Loc" label and the
keypad locks automatically.
4.2
Unlocking the keypad
Tap any key for 1 s. The display shows the label "UnL".
4.3
Setting the setpoint
Check that the keypad is not locked.
1.
2.
3.
4.4
Activating manual defrost (if r5 = 0, default)
Check that the keypad is not locked.
1.
If P4 = 1 (default), the defrost activates if the evaporator temperature is lower than the d2
threshold.
4.5
Turning the cabinet light on or off (if u0 = 3)
1.
5
ADDITIONAL FUNCTIONS
5.1
Navigating the additional functions menu
Before you begin, check that the keypad is not locked.
1.
2.
3.
4.
5.
6.
5.2
Additional functions menu
Use the additional functions menu to cycle through the labels in the following table.
LABEL
VALUE
CH
rCH
149
Pb1
Pb2
6
SETTINGS
6.1
Setting configuration parameters
1.
2.
3.
4.
5.
6.
7.
8.
9.
6.2
Restoring the default factory settings and storing customized settings as
default
Important
- Check that the factory settings are appropriate; see CONFIGURATION PARAMETERS.
- When you store customized settings, you overwrite the default.
1.
2.
3.
MIN. - MAX.
VAL.
r1 to r2
149
0 = °C
1 = °F
161
0 = Electric
1 = Hot gas
4.
2 = Compressor stopped
5.
6.
Description
Energy saving
n/a
Temperature unit of measurement
Compressor
Defrost
Evaporator fan
n/a
Auxiliary
On or standby
SET key and keypad lock
ON/STANDBY key, escape, and cabinet light
DOWN key and additional functions menu
UP key and defrost
If POF = 1, tap the ON/STAND-BY key for 4 s.
OFF
FLASHING
Compressor off
- Compressor protection active
- Setpoint setting active
-
- Defrost delay active
- Dripping active
Evaporator fan off
Evaporator fan stop active
-
Cabinet light on by digital input
-
-
-
-
Device on
Device on or off active
Tap the SET key.
Tap the UP or DOWN key within 15 s to set the value within the
limits r1 and r2.
Tap the SET key or do not operate for 15 s.
Tap the UP key for 2 s.
Tap the ON/STAND-BY key.
To access the additional functions menu, tap the DOWN key for
4 s.
To navigate to a label, tap the UP or DOWN key within 15 s.
To select a label, tap the SET key.
If you cannot edit the parameter, the value displays.
If you can edit the parameter, tap the UP or DOWN key to
navigate to the value that you want.
To set the parameter value, tap the SET key.
To exit the procedure, tap the ON/STAND-BY key, or do not
operate the controller for 60 s.
DESCRIPTION
View compressor functioning hours in hundreds
Delete compressor functioning hours
Command to delete compressor functioning hours
Cabinet temperature
Auxiliary temperature
Tap the SET key for 4 s. The display shows the label "PA".
Tap the SET key.
Tap the UP or DOWN key within 15 s to set the password. The
default password is "-19".
Tap the SET key or do not operate for 15 s. The display shows the
label "SP".
Tap the UP or DOWN key to select a parameter.
Tap the SET key.
Tap the UP or DOWN key within 15 s to set the value.
Tap the SET key or do not operate for 15 s.
Tap the SET key for 4 s, or do not operate for 60 s, to exit the
procedure.
Tap the SET key for 4 s. The display shows the label "PA".
Tap the SET key.
Tap the UP or DOWN key within 15 s to set the value.
DESCRIPTION
Restores the default factory settings
Stores customized settings as default
Tap the SET key or do not operate for 15 s. The display shows the
label "dEF" when you set the value "149" or the label "MAP"
when you set the value "161".
Tap the SET key.
Tap the UP or DOWN key within 15 s to set "4".
7.
Tap the SET key or do not operate for 15 s. The display shows "-
- -" flashing for 4 s, then the device exits the procedure.
8.
Interrupt the power supply to the device.
9.
Tap the SET key 2 s before step 6. to exit the procedure
beforehand.
7
ALARMS
COD.
DESCRIPTION
RESET
REMEDIES
Pr1
Cabinet probe alarm
Automatic
- Check P0
Pr2
Auxiliary probe alarm
Automatic
- Check probe integrity
- Check electrical connection
AL
Low temperature alarm
Automatic
Check A1
AH
High temperature alarm
Automatic
Check A4
id
Open door alarm
Automatic
Check i0 and i1
COH
High condenser temperature
Automatic
Check C6
warning
CSd
High condenser temperature
Manual
- Switch the device off and on
alarm
- Check C7
iA
Multi-purpose input alarm
Automatic
Check i0 and i1
dFd
Defrost timeout alarm
Manual
- Tap any key
- Check d2, d3, and d11
8
ELECTRICAL RATINGS
Output
Units
cULus (UL 60730)
Applied voltage at 60 Hz
120 VAC
K1
Resistive amperes
12
compressor
Inductive amperes
relay
Full load amperes
10
Locked rotor amperes
60
K2
Resistive amperes
8
defrost or
Inductive amperes
evaporator
Full load amperes
4.4
fan or
Locked rotor amperes
26.4
configurable
relay
9
TECHNICAL SPECIFICATIONS
Purpose of the control device
Function controller
Construction of the control device
Built-in electronic device
Container
Black, self-extinguishing
Category of heat and fire resistance
D
Measurements
75 mm x 33 mm x 59 mm (2 15/16 in. x 1
5/16 in. x 2 5/16 in.)
Mounting methods for the control device
Fit the controller to a panel with the snap-in
brackets supplied
Degree of protection provided by the covering IP65 in front
Connection method
Fixed screw terminal blocks for wires up to
2.5 mm²
Maximum permitted length for connection cables
Power supply: 10 m (32.8 ft)
Analog inputs: 10 m (32.8 ft)
Digital inputs: 10 m (32.8 ft)
Digital outputs: 10 m (32.8 ft)
Operating temperature
From 0°C to 55°C (from 32°F to 131°F)
Storage temperature
From -25°C to 70°C (from -13°F to 158°F)
Operating humidity
Relative humidity without condensate from
10% to 90%
Pollution status of the control device
2
Compliance
Europe
Johnson Controls declares product compliance meets requirements of EMC,
LVD, and RoHS Directives.
USA
UL Recognized Component, SDFY2.SA516; FCC Part 15 Subpart B Class A
Canada
UL Recognized Component, SDFY8.SA516; ICES-003 Class A
Power supply
TC3B22N7x
230 VAC (+10% -15%), 50/60 Hz (+/- 3Hz), max. 2 VA
Grounding methods for the control device
None
Rated impulse-withstand voltage
4 KV
Over-voltage category
III
Software class and structure
A
Analog inputs
2 for NTC probes (cabinet probe and auxiliary
probe)
NTC probes
Sensor type
ß3435 (10 kohm at 25°C, 77°F)
Measurement field
-40°C to 105°C (-40°F to 221°F)
Resolution
0.1°C (1°F)
Digital inputs
1 dry contact (door switch/multi-purpose)
Dry contact
Contact type
Power supply
Protection
Digital outputs
2 electro-mechanical relays
Type 1 or Type 2 actions
Type 1
Additional features of Type 1 or Type 2 actions C
Display
3-digit custom display with function icons
10
PRODUCT WARRANTY
This product is covered by a limited warranty, details of which can be found at
www.johnsoncontrols.com/buildingswarranty
11
SOFTWARE TERMS
Use of the software that is in (or constitutes) this product, or access to the cloud, or hosted
services applicable to this product, if any, is subject to applicable end-user license, open-
source software information, and other terms set forth at www.johnsoncontrols.com/techterms.
Your use of this product constitutes an agreement to such terms.
12
SINGLE POINT OF CONTACT
APAC
Europe
JOHNSON CONTROLS
JOHNSON CONTROLS
C/O CONTROLS PRODUCT
WESTENDHOF 3
MANAGEMENT
45143 ESSEN
NO. 32 CHANGJIJANG RD NEW
GERMANY
DISTRICT
WUXI JIANGSU PROVINCE
214028
CHINA
13
CONTACT INFORMATION
Contact your local branch office:
www.johnsoncontrols.com/locations
Contact Johnson Controls:
www.johnsoncontrols.com/contact-us
Important
The device must be disposed of according to local regulations governing the collection
of electrical and electronic waste.
This document and the solutions contained therein are the intellectual property of Penn and thus
protected by the Italian Intellectual Property Rights Code (CPI). Penn imposes an absolute ban on the
full or partial reproduction and disclosure of the content other than with the express approval of Penn.
The customer (manufacturer, installer or end-user) assumes all responsibility for the configuration of the
device. Penn accepts no liability for any possible errors in this document and reserves the right to make
any changes, at any time without prejudice to the essential functional and safety features of the
equipment.
CE (EN 60730)
240 VAC
240 VAC
12
10
2
10
60
8
5
2
2.9
17.4
5 VDC, 1.5 mA
None
None
NA/SA
JOHNSON CONTROLS
507 E MICHIGAN ST
MILWAUKEE WI 53202
USA

Publicidad

loading

Resumen de contenidos para Penn TC3B22

  • Página 1 Penn | TC3B22 | Installation Guide Rev. A | Part No. 24-7664-03868 | Page 1 of 14 | January 20, 2022 TC3B22 Basic Defrost Controller European Installation Guide Basic controller for refrigerated cabinets, with energy-saving strategies Make the electrical connection as shown in ELECTRICAL CONNECTION without powering Tap the SET key or do not operate for 15 s.
  • Página 2 Penn | TC3B22 | Installation Guide Rev. A | Part No. 24-7664-03868 | Page 2 of 14 | January 20, 2022 Nastavení žádané hodnoty Způsob připojení Neodnímatelná šroubová svorkovnice pro Zkontrolujte, zda není klávesnice zamknutá. vodiče do 2,5 mm² CEŠTINA Stiskněte tlačítko SET (NASTAVIT).
  • Página 3 Penn | TC3B22 | Installation Guide Rev. A | Part No. 24-7664-03868 | Page 3 of 14 | January 20, 2022 Aktivering af manuel afisning (hvis r5 = 0, standard) Overensstemmelse Kontrollér, at tastaturet ikke er låst. Europe Johnson Controls erklærer, at produktet opfylder kravene i EMC-, LVD- og DANSK RoHS-direktiverne.
  • Página 4 Penn | TC3B22 | Installation Guide Rev. A | Part No. 24-7664-03868 | Page 4 of 14 | January 20, 2022 Verdichterrelais Induktive Ampere — — Entsperren der Tastatur Drücken Sie 1 Sekunde lang auf eine beliebige Taste. Das Display zeigt „UnL“ an.
  • Página 5 Penn | TC3B22 | Installation Guide Rev. A | Part No. 24-7664-03868 | Page 5 of 14 | January 20, 2022 Desbloqueo del teclado Métodos de montaje del dispositivo de control Instale el controlador en un panel utilizando Pulse cualquier tecla durante 1 s. La pantalla muestra la etiqueta "UnL".
  • Página 6 Penn | TC3B22 | Installation Guide Rev. A | Part No. 24-7664-03868 | Page 6 of 14 | January 20, 2022 Déverrouillage du clavier 0,25 cm CARACTÉRISTIQUES ÉLECTRIQUES Appuyer sur n’importe quelle touche pendant 1 s. L’écran affiche « UnL ».
  • Página 7 Penn | TC3B22 | Installation Guide Rev. A | Part No. 24-7664-03868 | Page 7 of 14 | January 20, 2022 Impostazione del setpoint Metodo di connessione Blocchi terminali a vite fissi per fili fino a Verificare che il tastierino non sia bloccato.
  • Página 8 Penn | TC3B22 | Installation Guide Rev. A | Part No. 24-7664-03868 | Page 8 of 14 | January 20, 2022 Toetsenblok ontgrendelen Afmetingen 75 mm x 33 mm x 59 mm (2 15/16 in. x 1 Houd 1 seconde een willekeurige toets ingedrukt. Op het display wordt het label “UnL”...
  • Página 9 Penn | TC3B22 | Installation Guide Rev. A | Part No. 24-7664-03868 | Page 9 of 14 | January 20, 2022 Kontrollenhetens jording Ingen Slå kabinettlyset på eller av (hvis u0 = 3) NORSK Nominell impulsmotstandsspenning 4 KV Trykk på PÅ/HVILEMODUS-tasten.
  • Página 10 Penn | TC3B22 | Installation Guide Rev. A | Part No. 24-7664-03868 | Page 10 of 14 | January 20, 2022 Odblokowywanie klawiatury Wymiary 75 mm x 33 mm x 59 mm (2 15/16 cala x 1 Nacisnąć dowolny klawisz i przytrzymać przez 1 s. Na wyświetlaczu jest wyświetlana etykieta...
  • Página 11 Penn | TC3B22 | Installation Guide Rev. A | Part No. 24-7664-03868 | Page 11 of 14 | January 20, 2022 Desbloquear o teclado Métodos de montagem do dispositivo de Instale o controlador num painel com os Toque numa tecla qualquer durante 1 s. O visor exibe a etiqueta "UnL".
  • Página 12 Penn | TC3B22 | Installation Guide Rev. A | Part No. 24-7664-03868 | Page 12 of 14 | January 20, 2022 Manuaalisen sulatuksen aktivoiminen (jos r5 = 0, oletus) Vaatimustenmukaisuus Tarkista, ettei näppäimistöä ole lukittu. Eurooppa Johnson Controls ilmoittaa, että tuote täyttää EMC-, LVD- ja RoHS-direktiivien SUOMI vaatimukset.
  • Página 13 Penn | TC3B22 | Installation Guide Rev. A | Part No. 24-7664-03868 | Page 13 of 14 | January 20, 2022 Aktivera manuell avfrostning (om r5 = 0, standard) Styrenhetens föroreningsstatus Kontrollera att knappsatsen inte är låst. SVENSKA Överensstämmelse Tryck på UPP-knappen i 2 sek.
  • Página 14 Penn | TC3B22 | Installation Guide Rev. A | Part No. 24-7664-03868 | Page 14 of 14 | January 20, 2022...