Refrigerant piping
-
Secure the indoor unit using the nuts, washers.
Gas piping
connection
Liquid piping
Panel (to be installed
Drain piping
later, shown only as
connection
a reference)
N O T E
If a false ceiling has already been installed, complete all pi-
ping and wiring work inside the ceiling before hooking-up the
indoor unit.
Secure the indoor unit using the nuts, flat washers and spring
washers. (These nuts and washers are supplied, 4 pieces
each)
Adjusting the space between indoor units and false

 
ceiling opening
-
Adjust the indoor unit to the correct position while chec-
king with the pattern for installation.
Checking scale for dimension of opening
4 REFRIGERANT PIPING
4.1 PIPING CONNECTION
4.1.1 Piping Position
Position of piping connection is the following, which is available
from all directions, top, left or right.
9
PMML0280A rev.1 - 09/2014
Suspension bolts (4)
False ceiling
Suspension
bracket
Open the knockout
hole for wiring (Ø32,5)
Wiring hole (30x30)
Pattern board for installation
Packing (Corrugated board)
For ceiling already completed with panels.

 
Attach this side of the
scale to the inner side of
the opening of the ceiling
Indoor unit
Attach this side of
the scale to the
outer side of the unit
Checking scale
Check the dimension
of opening at each
side of the unit
Ceiling not completed with panels yet.

 
Pattern paper for installation
Dimension
for opening
Suspension bolt
Surface of ceiling
-
Tighten the nuts of the suspension brackets after the ad-
justment is completed. Apply LOCK-TIGHT paint to the
bolts and nuts in order to prevent them from loosening. If
not done, abnormal noises or sounds may occur and the
indoor unit may come loose.
4.1.2 Size of piping connection
Piping size

 
 Gas piping
RCI-1.0/1.5
Ø 12.70 (1/2)
RCI-2.0
Ø 15.88 (5/8)
RCI-2.5-6.0
Thickness of Copper Pipes

 
Nominal Diameters
Outer Diameters
1/4
3/8
1/2
5/8
Attach this side of the scale to
the lower side of the unit
Indoor unit
Attach this side
of the scale to
Ceiling panel
the ceiling panel
Checking scale
Check the height of the
ceiling at each corner of
the unit
Dimension
for opening
Unit
Screw (M6)
Pattern board for installation
mm (in)
 Liquid piping
Ø 6.35 (5/8)
Ø 9.53 (3/8)
(mm)
Thickness
6.35
0.80
9.53
0.80
12.70
0.80
15.88
1.00