8�0 DATA SHEET
MODEL
PERFORMANCE - Air 27°C Water 27°C RH 80%
Heating capacity
COP Range
Average COP at 50% Speed
PERFORMANCE - Air 15°C Water 26°C RH 70%
Heating capacity
COP Range
Average COP at 50% Speed
TECHNICAL SPECIFICATION
Operating air temperature
POWER SUPPLY
Rated input power
Rated input current
Maximum input current
Rated RCD type F
Rated Fuse aM/ MCB type C
Sound level at 10m
Recommended water flow rate
Water connection
GENERAL DATA
Net dimension LxWxH
Packed dimension LxWxH
Net weight
HERMETIC SYSTEM
Refrigerant charge R32
Minimum area requirement
NOTES
Heat pump performance parameters are subject to change without notice.
Always refer to the nameplate.
Global warming potential (GWP) R32 - 675.
The data is subject to modification without prior warning.
1005759 ISSUE 5
UNITS
VPT 12ALX
14.1
13.5-6.28
9.7
kW
10.64
8.5-5.11
6.5
C
230V Single Phase 50Hz
kW
0.20-2.24
A
1.21-8.9
A
12.5
mA
30
A
16
dB(A)
<29
m3/h
4.97
mm
mm
650x650x835
mm
670x670x870
kg
70
g
800
m2
5.4
VPT 16ALX
VPT 22ALX
18.5
24.4
13.5-6.03
13.5-5.14
9.3
8.8
13.61
17.8
8.4-5.02
6.2-4.14
6.4
4.7
-5°C to 43°C
0.23-3.06
0.75-4.75
1.23-12.0
3.45-19.6
15.5
24.5
30
30
20
32
<30
<30
6.5
8.98
1 1/2" and 50mm
650x650x835
745x752x967
670x670x870
770x770x980
80
95
800
1700
5.4
24.6
27

Publicidad