7. Specifications - 4.5kVA/6kVA
Rating Capacity(kVA/kW)
INPUT
Voltage Range
(With derating range)
Frequency
Phase/Wire
Power Factor
Current THD (100% linear load)
OUTPUT
Voltage Window
Frequency Regulation
Voltage Regulation
Capacity
Rated Power Factor
Sine Waveform
Distortion
Frequency Stability
Transfer Time
Crest Factor
Efficiency (AC to AC, Normal)
Efficiency (AC to AC, ECO)
DC Start
Bypass Voltage Windows
4.5kVA
110 ~ 300 V
De-rating 50%
Capacity
De-rating 75%
Capacity
100% Load Capacity
Single-in, Line + Neutral + Ground
Up to 0.99 at 100% Linear Load
100~127 / 200~240 V
±1Hz, ±3Hz Selectable
100%
Linear Load
4500 VA
100% Liner Load
100%
Non-Liner Load
<0.2% (Free Running)
3:1 Acceptable
Up to 94.5%
Inv.
240V
Low: ±15%
230V
High: ±10%
220V
208V
42
6kVA
AC
110 - 160Vac
160 - 176Vac
176 - 300Vac
40 ~ 70 Hz
< 3%
Selectable
AC
w/o TX
w/ TX
6000 VA
1.0
w/o TX
w/ TX
w/o TX
w/ TX
0 ms
Up to 98%
Yes
Range
L
276~204±5Vac
H
264~216±5Vac
264.5~195.5±5
L
H
253~207±5Vac
L
253~187±5Vac
H
242~198±5Vac
L
239.2~176.8±5
±1%
±3%
<1%
<2%
<4%
<6%
Vac