8. Specifications - 8kVA/10kVA
Rating Capacity
INPUT
Voltage Range
(With derating range)
Frequency
Phase/Wire
Power Factor
Current THD (100% linear load)
OUTPUT
Voltage Window
Frequency Regulation
Voltage Regulation
Capacity
Rated Power Factor
Sine Waveform
Distortion
Frequency Stability
Transfer Time
Crest Factor
Efficiency (AC to AC, Normal)
Efficiency (AC to AC, ECO)
DC Start
Bypass Voltage Windows
(kVA/kW)
De-rating 50%
De-rating 75%
Linear Load
100% Liner Load
Non-Liner Load
Low: ±15%
High: ±10%
45
8kVA
110 ~ 300 V
Capacity
Capacity
100% Load
Capacity
40 ~ 70 Hz
Single-in, Line + Neutral + Ground
Up to 0.99 at 100% Linear Load
<5%
100~127 / 200~240 V
±1Hz, ±3Hz Selectable
100%
w/o TX
w/ TX
8000 VA
w/o TX
w/ TX
w/o TX
100%
w/ TX
<0.2% (Free Running)
0 ms
3:1 Acceptable
Up to 94.5%
Up to 98%
Inv.
L
240
V
H
L
230
V
H
L
220
V
H
208 L
10kVA
AC
110 - 160Vac
160 - 176Vac
176 - 300Vac
Selectable
AC
±1%
±3%
10000 VA
1.0
<1%
<2%
<4%
<5%
Yes
Range
276~204±5Vac
264~216±5Vac
264.5~195.5±5Vac
253~207±5Vac
253~187±5Vac
242~198±5Vac
239.2~176.8±5Vac