ASD30 Wireless Smoke Detector
Installation and Operating Instructions
Read this instruction sheet thoroughly before installation and use of the ASD30
Introduction
The ASD30 is a wireless photoelectric smoke detector with a rate of rise heat detector and an
internal piezoelectric alarm.
Compatible Devices
This smoke detector is compatible with the following Bentel Wireless Control Panels and Wireless
Receivers: VECTOR/RX8, VRX32-433 e VRX32-433EN.
Operation
Approximately every 7 to 8 seconds the unit tests for a smoke or heat alarm condition. During this
sequence the unit also performs self diagnostics, and checks for tampers and faults. During normal
operation the green LED will flash every 12 seconds and the sounder will not sound.
Smoke Alarm
The smoke detector will go into alarm when the signal level exceeds the "alarm" threshold and auto-
matically restore when the signal level falls below the alarm "restore" threshold. During an alarm
the LED will flash 1/second and the sounder will sound the evacuation temporal pattern.
Alarm Silencing
This smoke alarm is provided with an automatically resettable alarm silencing feature. When the
sensor is in alarm, by pressing the Test/Silence/Reset button it will silence the local annunciation of
the alarm and transmit an alarm restoral event to the control panel. The LED will flash every 8
seconds (for up to 10 minutes) to indicate the alarm has been silenced.
The flashing LED will stop when the unit returns to normal operation. The alarm silence feature has
a fixed time setting that desensitizes the smoke alarm for 8 minutes.
Alarm silencing does not disable the smoke alarm but rather reduces its smoke sensitivity. Fol-
lowing the silenced period the smoke alarm restores automatically to its intended operation. If
smoke around the unit is dense enough to suggest a potentially dangerous situation, it will stay in
alarm, or may return to the alarm state quickly.
Detector Trouble
When the detector has a general fault, the yellow LED blinks once every four seconds and there is
a chirp every 48 seconds. After 12 hours, the panel will display a loss of supervision message.
NOTE: The sounder and LED are not synchronised.
Status
LEDs
Normal
Green flash every 12 seconds
Heat Alarm
Red flash every second
Heat Test
Red flash every second
Smoke
Red flash every second
Alarm
Smoke Test
Red flash every second
Sounder
Off
ANSI S3.41 temporal 3
ANSI S3.41 temporal 3
ANSI S3.41 temporal 3
(press button to hush for 5-10 minutes)
ANSI S3.41 temporal 3
(press button to hush for 5-10 minutes)