• Because of the IP20 protective system used, the device must be operated in dry
rooms only.
• Only appliances with protection class III (SELV) may be connected to the unit.
• During the warranty period, the factory-set output voltage 24V may only be
changed by the Franke-Aquarotter customer service department.
• Secure the electric connection with an earth leakage circuit breaker (RCD).
• Proper cooling must be assured. To ensure an unimpeded flow of cooling air, it is
important to maintain a minimum distance of 15 mm to adjacent equipment.
• All rights reserved to make technical alterations.
5.

Application

ECC2 Function Controller - A3000 open with Ethernet and CAN bus connection. For
connecting AQUA 3000 open fittings/electronic system modules for the purpose of
supplying power and external control, such as settings for fittings and communi-
cation. For mounting on a 35 mm DIN rail in the on-site switch-gear cabinet
(provided by customer), for wall mounting or in an electrical distribution system in
accordance with the applicable VDE regulations.
Functions of integrated digital inputs with LED status display:
– Control for thermal disinfection
– Acknowledgment of collective fault signals
– Switching program modes (e.g. night mode or holiday mode)
Functions of the integrated potential-free digital outputs with LED status display:
– Control for thermal disinfection
– Display of collective fault signals
Storage of statistical data with date and time, can be read via the USB interface in
csv format.
Additional functions can be set via a web browser:
– Switch-off for cleaning
– Triggering hygiene flushing
– Simultaneity suppression
– Sequential controls
– System flushing
– Reduction in flow duration
- 5 -