Descargar Imprimir esta página

Eaton GH5 Manual Tecnico página 5

Publicidad

Idiomas disponibles

Idiomas disponibles

Recycling
Complete disposal of the device is done as electronics waste. When dismantling the device, the plastic, metal and
electronic components must be disposed of separately.
Connection
Loosen the two cover screws with an Allen key size 4 and remove the cover. Before connecting the Light make sure the
conductors of the power cable are dead (no voltage). The power cable is fed through the cable gland to the interior of
the enclosure and is fixed with the screw part of the cable gland. Inside the en - closure there are the terminals on the
printed circuit board. After having set up the connection, please fix the cover to the housing and tighten the screws with
a torque of 0.9 ... 1.1 Nm.
For Multicolour Lights with operating voltage 230 V
Connect the neutral connector to the terminal marked „N" . Connect the white, blue, red, yellow and green operating
voltage conductors to the accordingly marked terminals.
Terminals with 230 V
gn ye rd bl wh N
For Multicolour Lights with operating voltage 24 V
Connect the 0 V or the negative cable conductor to the terminal designated with „GND" . Connect the cable conductors
with positive voltage corresponding to the colours white, blue, red, yellow, and green to the accordingly designated
terminals.
Terminals with 24 V
DC
gn
As far as the set up of the Multicolour Light by means of the slide switches has not taken place yet, go to chapter
„Settings" . Otherwise fix the cover to the housing and tighten the screws with a torque of 0.9 ... 1.1 Nm.
Settings
Before making the setting, make sure the Multicolour Light is disconnected (no voltage).
When the enclosure is open, (a) circuit board(s) are visible. On one side are the terminals described under
„Connection" and on the other side is a block of 10 slide switches marked 1...10, for setting the operating mode of
the individual colours (white, blue, red, yellow, green).
Slide switch (slider drawn
in white, as-shipped state)
AC
ye
rd
bl
wh GND
1 2 3 4 5 6 7 8 9 10
wh
bl
white
blue
GH5 ACTIVELINE BEACON TECHNICAL MANUAL
GH5 Activeline Beacon Technical Manual
AC
230 V
AC
DC
24 V
DC
rd
ye
gn
red
yellow
green
TMF0075.A
www.eaton.com
5

Publicidad

loading