Casals CTRL-DPH Manual De Usuario Y Programación página 30

Tabla de contenido

Publicidad

91
DP _SUPPLY
92
DP _EXHAUST
93
FLOW_SUPPLY
94
FLOW_EXHAUST
95
FAN_HOURS_H
96
FAN_HOURS_L
97
ALARMS 2
98
PRE_HEAT
99
POST_HEAT
101
TEMP_E
141
TEMP_E
1001
TIME_TABLE_SPEED_0
1002
TIME_TABLE_SPEED_1
1003
TIME_TABLE_SPEED_2
1017
MONDAY-CHANGE-0
1024
/ 7
1025
TUESDAY-CHANGE-0
1032
/ 7
1033
WEDNESDAY-CHAN-
1040
GE-0 / 7
1041
THURSDAY-CHANGE-0
1048
/ 7
1049
FRIDAY-CHANGE-0 / 7
1056
1057
SATURDAY-CHANGE-0
1064
/ 7
CV072018-1
B15: DPEXHAUST_FAIL
(Pa)
(m3/h)
(m3/h)
(65536 h)
(h)
B00: CONFIGURATION_FAIL
B01: ANTI ICE_FAIL
(%)
(%)
UNIDAD_2_DATOS
UNIDAD_4_DATOS
IF CONFIG_FLAGS_1.MODULE_FLAG = 0 :
0-1-2-3) OR AUTO(5)
IF CONFIG_FLAGS_1.MODULE_FLAG = 1
and PRESS_FLOW_REG_PRESENT = 0 :
0-100% OR AUTO(102)
IF CONFIG_FLAGS_1.MODULE_FLAG = 1
AND PRESS_FLOW_REG_PRESENT = 1 :
0 - SPEED_RANGE OR
AUTO(65535)
B00-10: TIME - MINUTES
B11-13: SPEED SELECTION :
000: TIME_TABLE_SPEED_0
001: TIME_TABLE_SPEED_1
002: TIME_TABLE_SPEED_2
B14-15: TEMPERATURE REG. ENABLE
00: OFF
01: ON
PARA UNIDADES COP = VALOR DE
PRESIÓN LADO VENTILADOR IMPULSIÓN
PARA UNIDADES COP = VALOR DE
PRESIÓN LADO VENTILADOR RETORNO
PARA UNIDADES CAV = VALOR DE CAUDAL LADO
VENTIL. IMPULSIÓN
PARA UNIDADES CAV CON DOBLE SONDA = VA-
LOR DE CAUDAL LADO VENTIL. RETORNO
TIEMPO DE FUNCIONAMIENTO VENTILADORES
(FAN_HOURS_H * 65536+ FAN_HOURS_L)
ERROR DE CONFIGURACIÓN ALARMA ANTIHIELO
PORCENTAJE REGULACIÓN PRECALENTAMIENTO
.
MODUL
PORCENTAJE REGULACIÓN POSCALENTAMIENTO
MODUL
R
R
SELECCIÓN DE LA VELOCIDAD A
RW
ASOCIAR A LA FRANJA HORARIA
IAJUSTE TIEMPO EN MINUTOS DESDE
00.00 (EJ.:60=1.00)
RW
SELECCIÓN DE LAS VELOCIDADES
SELECCIÓN TEMPERATURAS
RW
COMO LA ANTERIOR
RW
COMO LA ANTERIOR
RW
COMO LA ANTERIOR
RW
COMO LA ANTERIOR
RW
COMO LA ANTERIOR
30