INSTRUCTION SHEET
VERIFICADOR DE PDC SIXXI, (SI-TESTER)
Descripción y objetivo
Supervise fácilmente in situ el estado del Pararrayos con Dispositivo de Cebado nVent ERICO System 1000 (SIXXi)
El resultado de la prueba se muestra en resumen con la visualización de <OK> (led verde) o <Default> defecto (led rojo).
El verificador es autónomo y funciona con una pila estándar de 9 V, tipo PP3, que se coloca en la parte posterior de la
carcasa. En caso de fallo de la pila, <Bat> (led amarillo) parpadea, entonces, la pila debe cambiarse.
Función de los botones e indicadores
1
3
2
4
5
5
Especificaciones eléctricas
•
Verificación del circuito del pararrayos con un impulsos
•
Tensión máxima: 1.2 kV
•
Corriente máxima: 100 AA
Características mecánicas
•
Caja de plástico resistente al agua: IP56
•
Dimensiones: L 149 mm, D 89 mm, H 26 mm
•
Peso: 280 g
•
Se suministra con dos cables de prueba con pinzas de cocodrilo.
•
El SI-TESTER-POLE es una percha telescópica, de 9 m de largo desplegada y longitud plegada de 2,55 m, para
poder alcanzar los PDC a una altura de 10 m.
Instrucciones
El uso in situ se limita a conectar el terminal rojo del verificador a la punta del pararrayos (directamente con las pinzas o
mediante el cable blanco de la percha SI-TESTER-POLE) y el segundo en negro, con las pinzas, al cuerpo del pararrayos,
a su mástil, o al conductor descendente más cercano al que está conectado.
La prueba se lleva a cabo presionando los 2 botones con el logotipo nVent presente de la carcasa (con ambas manos para
no tocar el pararrayos durante la prueba) durante un período de aproximadamente 6 segundos, hasta que aparezca el
resultado de la prueba que da como resultado el encendido intermitente verde <OK> o el rojo <Default> (defectuoso).
WARNING:
1. nVent products shall be installed and used only as indicated in nVent product instruction sheets and training materials. Instruction sheets are available at www.nVent.com and from your nVent
customer service representative.
2. nVent products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.
3. All instructions must be completely followed to ensure proper and safe installation and performance.
4. Improper installation, misuse, misapplication or other failure to completely follow nVent's instructions and warnings may cause product malfunction, property damage, serious bodily injury and/or death,
and void your warranty.
SAFETY INSTRUCTIONS: All governing codes and regulations and those required by the job site must be observed. Always use appropriate safety equipment such as eye protection, hard hat, and
gloves as appropriate to the application.
nVent, nVent CADDY, nVent ERICO Cadweld, nVent ERICO Critec, nVent ERICO, nVent ERIFLEX, and nVent LENTON are owned by nVent or its global affiliates. All other trademarks are the
property of their respective owners. nVent reserves the right to change specifications without prior notice.
TECHNICAL SUPPORT:
www.nVent.com
1.
Bornes de conexión para los cables hacia el Pararrayos con Dispositivo de Cebado
2.
La luz roja intermitente al final de la prueba indica que el pararrayos está en mal estado.
3.
La luz verde intermitente al final de la prueba indica que el pararrayos está en buen estado.
4.
Luz amarilla que indica el estado de la batería. LED encendido significa "pila en buen
estado" y parpadeando "reemplazar la pila"»
5.
Botones para iniciar la verificación.
IP8564_A
©
5 of 6
2020 nVent All Rights Reserved