Check method
On the remote controller (Main remote controller, Central control remote controller) and the interface P.C. board of
the outdoor unit, a check display LCD (Remote controller) or 7-segment display (on the outdoor interface P.C.
board) operation is provided. Therefore the operation status can be known. Using this self-diagnosis function, a fault
and the location of this fault within the air conditioning system can be located, as shown in the table below.
Check code list
The following list shows each check code. Find the check contents from the list according to part to be checked.
• In case of a fault from the indoor remote controller: See "Main remote controller display" in the list.
• In case of a fault from the outdoor unit: See "Outdoor 7-segment display" in the list.
• In case of a fault from the indoor unit with a wireless remote controller:
See "Sensor block display of receiving unit" in the list.
Check code
Main
Outdoor 7-segment display
remote
controller
display
Auxiliary code
E01
E02
E03
E04
No. of indoor units in which
E06
E06
sensor has been normally
received
E07
E08
E08 Duplicated indoor addresses
E09
E10
01: Indoor/Outdoor
communication
E12
E12
02: Communication between
outdoor units
E15
E15
00: Capacity over
E16
E16
01 ~: No. of connected units
E18
00: Header is nothing
E19
E19
02: Two or more header units
01: Outdoor of other line
connected
E20
E20
02: Indoor of other line
connected
E23
E23
E25
E25
E26 No. of outdoor units which
E26
received signal normally
E28
E28 Detected outdoor unit number
01: IPDU1 error
02: IPDU2 error
03: IPDU1, 2 error
E31
E31
04: Fan IPDU error
05: IPDU + Fan IPDU error
06: IPDU2 + Fan IPDU error
07: All IPDU error
All manuals and user guides at all-guides.com
AI-NET : Artificial Intelligence.
Terminology
IPDU : Intelligent Power Drive Unit
¡
: Lighting,
ALT. : Flashing is alternately when there are two flashing LED.
SIM : Simultaneous flashing when there are two flashing LED.
Wireless remote controller
Sensor block display
AI-NET central
of receiving unit
control display
Operation
Timer Ready Flash
¤
l
l
¤
l
l
¤
l
l
97
l
l
¤
04
l
l
¤
04
l
l
¤
¤
l
l
96
¤
l
l
99
¤
l
l
CF
¤
l
l
42
l
l
¤
42
l
l
¤
89
¤
l
l
97, 99
l
l
¤
96
l
l
¤
42
l
l
¤
15
l
l
¤
15
l
l
¤
15
l
l
¤
d2
l
l
¤
CF
24
l
¤
: Flashing,
: Goes off
Check code name
Communication error between indoor and remote
controller (Detected at remote controller side)
Remote controller transmission error
Communication error between indoor and remote
controller (Detected at indoor side)
Communication circuit error between indoor/outdoor
(Detected at indoor side)
Decrease of No. of indoor units
Communication circuit error between indoor/outdoor
(Detected at outdoor side)
Duplicated indoor addresses
Duplicated main remote controllers
Communication error between indoor MCU
Automatic address start error
Indoor is nothing during automatic addressing
Capacity over / No. of connected indoor units
Communication error between indoor units
Outdoor header units quantity error
Other line connected during automatic address
Sending error in communication between outdoor units
Duplicated follower outdoor addresses
Decrease of No. of connected outdoor units
Follower outdoor unit error
IPDU communication error
Judging device
Remote controller
Remote controller
Indoor
Indoor
I/F
I/F
Indoor / I/F
Remote controller
Indoor
I/F
I/F
I/F
Indoor
I/F
I/F
I/F
I/F
I/F
I/F
I/F