Leakage relay type ABS CA 461, Installation guide
EN
2
TECHNICAL DATA
2.1
Technical data CA 461
Leakage sensor voltage
Max sensor current
Leakage detection threshold
Alarm on delay
Ambient operating temperature
Ambient storage temperature
Degree of protection
Housing material
Mounting
Installation category
Pollution degree
Flame rate
Humidity
Dimensions
Power supply
Fuse
Terminal wire size
Terminal tightening torque
Power consumption
Max load output relay
Altitude
Compliance
Attention If the unit is used in a manner not described in this document the protection
provided by the equipment may be impaired.
2.2 Cleaning
How to clean the unit
Powers off the unit and only outside/front shall be cleaned by using a dry, soft
cloth. A good choice would be the microfiber type of cloth. Gently wipe the
CA 461 unit front in order not to scratch the overlay. If the dry cloth did not com-
pletely remove the dirt, do not press harder in an attempt to scrub it off.
If necessary, moisten the cloth by adding a small amount of water with thin
solution of mild detergent and try again. Never use detergent with polish or
solvent which can have an impact of the plastic surface.
12 VDC
< 15 µA
< 100 kohm
10 seconds
–20 to +50 °C (–4 to +122 °F)
–30 to +80 °C (–22 to +176 °F)
IP 20, NEMA: Type 1
PPO and PC
DIN Rail 35 mm
CAT II
2
V0 (E45329)
0–95% RH non-condensing
H x W x D: 108 x 35 x 58 mm
(4.25 x 1.38 x 2.28 in.)
16907010
110-230 VAC
16907011
18 - 36 VDC, SELV or Class 2
Max 10 A
Use copper (Cu) wire only. 0.2 - 2.5 mm
flexible core, stripped length 8 mm.
0.56 - 0.79 Nm (5 - 7 lbs-in)
< 2 W
250 VAC 3 Ampere
Max 2000 MASL or 6562 ft. AMSL
4
2