5. Transport, packaging ... / 6. Commissioning, operation
5. Transport, packaging and storage
5.1 Transport
Check the air flow transmitter for any damage that may have been
caused by transport. Obvious damage must be reported immediately.
5.2 Packaging
Do not remove packaging until just before mounting.
Keep the packaging as it will provide optimum protection during
transport (e.g. change in installation site, sending for repair).
5.3 Storage
Permissible conditions at the place of storage
Storage temperature: -20 ... +70 °C
Protect the instruments from moisture and dust.
6. Commissioning, operation
Output signal
V OUT DC 0 ... 10 V, P OUT DC 0 ... 10 V
Load R minimum 1 kΩ linear to the set output unit
Supply voltage
AC 24 V or DC 24 V ±10 %
Electrical connection
Cable gland M16, screw terminals max. 1.5 mm²
WIKA operating instructions air2guide model A2G-25
V scale output
can be changed
(in relation to
the selected
output unit)
GB
9