4.
FUNCTIONS
4.1 SERVICE OUTPUT
The SERVICE Output is programmable from the Installer MENU of parameter
P02:
• P02 = 0 DISABLED: the output does not work
• P02 = 1 THERMOSTAT: the output is active if the temperature of the S1 Pro-
be is greater than the E07 thermostat
• P02 = 2 GRILL: pressing the K3 button for 3 seconds you can turn on or turn
off the output
• P02 = 3 DAMPER: the output manages a damper for the adjustment of the
combustion air
• P02 = 4 SPARK: the output manages the spark control
The functions THERMOSTAT AND DAMPER are disabled in the case of P17 = 1
4.2 INPUT S2 CONFIGURATION
Using parameter P01 you can enable the following connection managers:
• P01 = 0, input S2 = DISABLED
• P01 = 1, input S2 = ROOM TEMP PROBE
• P01 = 2, input S2 = ROOM TEMP THERMOSTAT
4.3 FAN STARTING FUNCTION
This operation allows the Fan to operate at Maximum Speed for a program-
mable time (t08), every time that it has to start from a standstill. After the time
has lapsed the Fan will resume to programmed speed.
To disable the Fan Starting function, programme the time t08 to 0 seconds.