5. Commissioning, operation
5.4 Electrical connection
The electrical connection must only be made by qualified skilled
■
personnel.
EN
Wire the level sensor in accordance with the connection diagram of
■
the electrical output (see product label). The connection terminals are
appropriately marked.
Electrical output
3-wire potentiometer
circuit
4 ... 20 mA
Seal the cable bushing at the connection housing (see
■
illustration in chapter 5.3 "Mounting").
Always observe the mounting and operating instructions of accessories
when commissioning them.
14
WARNING!
Malfunctions through voltage spikes due to running cables
together with mains connection leads or due to large cable
lengths.
This can lead to a malfunction in the plant and thus lead to
injury to personnel or damage to equipment.
▶
Use shielded connection leads.
▶
Ground connection leads at one end.
Connection diagram
GN
BN
WH
+
R
I
–
WIKA operating instructions models RLT
4 ... 20 mA
A
DC 12 ... 32 V