Vertiv™ Liebert® GXT5 Lithium-Ion UPS 1000-3000VA
I, 230V In, 230V Out
Quick Installation Guide
2. Connecting UPS Input and
Output
The UPS has a IEC 60230-1 C14 or
C20 input plug depending on the
model. Input power cables are also
included with the UPS.
The UPS is equipped with output
receptacles. Connect the
equipment to be protected to the
output receptacles.
3. Connecting AC Input
Refer to the above overcurrent
protection table for the
recommended panel feeder
breaker. Connect to an input-power
source that is properly protected
by a circuit breaker in accordance
with national and local electrical
codes.
NOTE: Allow the batteries to
charge for at least two hours
before first start up to ensure
adequate backup time. Allow an
additional two hours of charging
for each EBC, if connected. The
batteries charge when the UPS is
connected to AC input regardless
of whether the UPS is on or off.
Powering the UPS
NOTE: Do not power on the UPS
until the installation is completed.
1. Make sure the panel feeder
breaker supplying power to
the UPS is closed.
2. If EBCs are connected, close
the breakers on the rear of
each EBC.
3. When the UPS is first
connected start up
guidance screens will
appear. Use the Up, Down,
and Enter buttons to
confirm settings. Then,
press and hold the power
button to power on the UPS.
Overcurrent Protection:
Wiring
Model
GXT5LI-1000IRT2UXL
GXT5LI-1500IRT2UXL
GXT5LI-2000IRT2UXL
GXT5LI-3000IRT2UXL
Operation and Display Panel
NOTE: The UPS alarm will sound
when the output receptacles are not
powered. Press and hold the ESC
button for two seconds to mute the
alarm.
Recommended Panel Feeder Breaker
10 A
16 A
20 A
Item
Description
1
Run
2
Alarm
3
Power button
4
Display screen
5
Escape button
6
Up button
7
Down button
8
Enter button
31014372/SL-70871_REVA_01-22
3