28
MicroLogix™ 1100 Programmable Controllers
Description
Surge Current per Point:
• peak current
• maximum surge duration
• maximum rate of repetition at 30°C (86°F)
• maximum rate of repetition at 65°C (149°F)
Turn-On Time (maximum)
Turn-Off Time (maximum)
Repeatability (maximum)
Drift (maximum)
(1)
Output 2 and 3 are designed to provide increased functionality over the other FET outputs. Output 2 and 3 may be used like
the other FET transistor outputs, but in addition, within a limited current range, they may be operated at a higher speed.
Output 2 and 3 also provide a pulse train output (PTO) or pulse width modulation output (PWM) function.
Working Voltage
Description
Power Supply Input to
Backplane Isolation
Input Group to Backplane
Isolation
Input Group to Input Group
Isolation
Output Group to Backplane
Isolation
Output Group to Output
Group Isolation
Publication 1763-IN001A-MU-P - May 2005
General Operation
• 4.0A
• 10 msec
• once every second
• once every 2
0.1 msec
1.0 msec
Not Applicable
Not Applicable
1763-L16AWA
Verified by one of the following dielectric tests: 1836V ac for 1 second or
2596V dc for 1 second
265V ac Working Voltage (IEC Class 2 reinforced insulation)
Verified by one of the following dielectric tests:1517V ac for 1 second or 2145V
dc for 1 second
132V ac Working Voltage (IEC Class 2 reinforced insulation)
Verified by one of the following dielectric tests:1517V ac for 1 second or 2145V
dc for 1 second
132V ac Working Voltage (basic insulation)
Verified by one of the following dielectric tests: 1836V ac for 1 second or
2596V dc for 1 second
265V ac Working Voltage (IEC Class 2 reinforced insulation)
Verified by one of the following dielectric tests: 1836V ac for 1 second or
2596V dc for 1second
265V ac Working Voltage (basic insulation), 150V ac Working Voltage (IEC
Class 2 reinforced insulation)
High Speed Operation
(Output 2 and 3 Only)
• Not Applicable
• Not Applicable
• Not Applicable
• Not Applicable
seconds
6 µsec
18 µsec
2 µsec
1 µsec per 5°C (9°F)
(1)