Commissioning, Operation; Mounting The Instrument - WIKA MH-1 Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

5. Commissioning, operation

5. Commissioning, operation

5.1 Mounting the instrument

EN
Requirements for mounting point
The mounting point must meet the following conditions:
Sufficient space for a safe electrical installation.
Permissible ambient and medium temperatures remain within the performance limits.
Consider possible restrictions on the ambient temperature range caused by mating
connector used.
→ For performance limits see chapter 9 "Specifications"
Sealing variants
Parallel threads
Seal the sealing face  with flat gasket, lens-type
sealing ring or WIKA profile sealing.
Tapered threads
Wrap threads with sealing material (e.g. PTFE
tape).
Mounting the instrument
1. Seal the sealing face (→ see "Sealing variants").
2
At the mounting point, screw the pressure transmitter in hand-tight.
.
3
Tighten with a torque spanner using the spanner flats.
.
10
The max. torque depends on the mounting point (e.g. material and shape).
If you have any questions, please contact our application consultant.
→ For contact details see chapter 1 "General information" or the back
page of the operating instructions.
WIKA operating instructions, pressure transmitter, model MH-1
per EN 837
NPT, R and PT
per DIN 3852-E

Publicidad

Tabla de contenido
loading

Tabla de contenido