ASSEMBLING THE HEATER

The manufacturer is not responsible for any harm or damage if attention is
not paid to the points described above.
The use of this product and the elements required for that purpose is entire-
ly at the end user's own risk.
HEATER LOCATION AND CLEARANCE
Always maintain: (Pic.1)
- 120 cm clearance from combustible materials,
- minimum 100 cm top clearance
- minimum 100 cm side clearance
- Heater must only be placed and used on a firm, level and stable under-
ground.
WARNINGS
Never use the heater while it is raining, the glass tube would break when it
suddenly met water.
Always turn off the heater while there is a rain.
Never splash any liquid to the glass tube when the heater is working.
The glass tube will be extremely hot when it is working, never try to touch it
and keep the children away from the heater.
Always ensure the heater stands firmly, the glass tube may break if the heat-
er was fell down onto ground.
Never use the heater if the glass tube has any crack.
GAS REQUIREMENTS
Use propane, butane or LGP only. See rating label on the appliance.
Maximum size of cylinder suitable for the appliance is Ø 32 cm x 59 cm (high).
Gas supply to the appliance from the gas cylinder: the appliance requires
approved gas hose in 60-80 cm length and a gas regulator. The hose and reg-
ulator assembly must conform to local standard codes.
Regulator maximum inlet pressure must not exceed 690 kPa.
Regulator outlet pressure to be 28 mbar (2.8 kPa) to 37 mbar (3.7 kPa)
depending on countries.
The installation must conform to local codes, or in the absence of local codes,
to the standard for the storage and handling of liquid petroleum gases.
A dented, rusted or damaged gas cylinder may be hazardous and should be
checked by an authorized dedicated gas specialist.
Never use a gas cylinder with a damaged valve connection.
The gas cylinder must be arranged to provide for vapor withdrawal from the
operating cylinder.
Never twist the flexible tubes and hoses.
Disconnect the gas cylinder when the heater is not use.
Do not connect the gas cylinder directly to the appliance without regulator
Use only the type of gas and the type of cylinder specified in these instruc-
tions
LEAK TESTING
Gas connections on the heater are leak tested at the factory prior to ship-