Sistema de batería de respaldo

Publicidad

Idiomas disponibles

Idiomas disponibles

Safety • Specifications
GENERAL INFORMATION
The Battery Backup Combo Kit is pre-plumbed up to
the hose and clamp assembly. The system includes the
primary sump pump (PSP), backup sump pump (BSP)
assembly, and vertical float switch. The unit is equipped
with two check valves - one for the primary pump and
one for the backup pump.
The battery backup pump is not a substitute for your
primary sump pump. It is designed to temporarily backup
your primary sump pump during a power outage or other
problem which prevents normal operation of the primary
pump. Do not use this system to pump flammable liquids
or chemicals. Pump clear sump water only with this
pump. For residential use only.
Keep the battery charger dry and protected from damage.
This system is designed to work with either a sealed
lead-acid AGM battery or a flooded lead-acid battery.
Use of a true Gel Cell (often confused for AGM) or a
standard automotive battery with this charger is not
recommended. An automotive battery may require
charging after only 1-2 hours of continuous use, and the
repeated charging cycles may cause early plate failure in
the battery.
Specifications
Maximum vertical pumping distance is 15 feet (4.6M) for
Model FG-3100RC.
Power supply required
Primary Sump Pump..........................115V, 60 HZ.
Backup Sump Pump........................12V DC Battery
Liquid Temp. Range..........................32°F to 70°F(0°-21°C)
Individual Branch Circuit Required (min.).............15 Amps
Discharge:
Hose & Clamp Assembly ...............1-1/4" Slip / 1-1/2" Slip
Minimum pit diameter ....................................................14"
Minimum depth...............................................................10"
NOTICE Do not reduce size of discharge pipe or hose
below 1-1/4" diameter. If discharge is too small, pump will
overheat and fail prematurely.
NOTICE: If a Carbon Monoxide (CO) sensor is installed,
it must be at least 15 feet away from battery charger
in order to avoid nuisance CO alarms. Please refer
to your CO detector's installation guidelines for more
information.
Performance - Primary
GPM (LPM) at total feet (m) of lift
5
Series
HP
(1.5m)
Capacity Gallons(L)/M
Primary
66
1/2
(HS50V1)
(250)
Performance - Backup
GPM (LPM) at total feet (m) of lift
0
Series
(0)
Capacity Gallons(L)/M
Backup
45
(PS17-2005)
(170)
Electrical & Switch Specifications
Motor
Full Load
Series
HP
Amps
HS50V1
1/2
4.1
PS17-2005
-
-
Required Battery Capacity:
For best results, use the following AGM Storage Batteries:
Part
Amp-Hour
BAT40
40
BAT75
75
• Unit equipped with dual battery capability
• Maximum amp-hour: 120
• 38-120 Ampere-Hour Storage or Deep Cycle Battery
10
15
20
(3m)
(4.6m)
(6.1m)
56
44
28
(212)
(167)
(106)
5
10
(1.5m)
(3m)
34
21
(129)
(80)
Branch
Switch Setting in
Circuit
inches (cm)
Req.
(Amps)
On
7.5
(19.1)
15
10.5
(26.7)
Gal/Charge
Approx Run
at 10'
Time
4,800
5 Hours
11,500
11.5 Hours
3
MAX.
LIFT
25
(7.6)
MAX.
LIFT
15
(4.6m)
Off
3
(7.6)
25 sec.