4. Enclosure Installation
4.2 Unpacking
Move shipping pallet to a firm, level surface.
1
Open box and remove the four foam corner protectors. Save all packing materials for later use unless you are certain they will not be required.
2
Packing materials are recyclable.
With one person on each side, carefully lift the enclosure out of the box and place on a firm, level surface.
3
Examine the enclosure for any damage or loose parts. Confirm all parts are present. If anything is missing or damaged, contact Tripp Lite for
4
assistance. Do not attempt to use the enclosure if it has been damaged.
Never extend more than one component from the enclosure at a time.
4.3 Placement
If using the optional casters, you can use the casters to move the enclosure for a short distance over a level, smooth, stable surface by pushing it from
the front or rear (not the side panels). Do not attempt to roll the enclosure over long distances. The enclosure should be moved close to its installation
location inside its shipping container before it is unpacked. Warning: Do not push or pull the enclosure at the side panels or pull the
enclosure toward you. Only experienced equipment operators should attempt to lift the enclosure. Use appropriate equipment and
follow all applicable safety procedures and regulations.
Warning: Never attempt to lift or install without adequate help.
4.4 Ground Connection
All parts of the enclosure are grounded to the frame of the enclosure. Use the enclosure's front or
rear threaded grounding point
directly to your facility's earth ground connection with an 8 AWG (3.264 mm) wire. Route the
ground wire under the enclosure's frame to ensure unhindered door operation. Warning: Attach
each enclosure to earth ground separately. Do not use the enclosure without an earth ground
connection.
continued
Use at least two people to unpack the enclosure.
Do not try lifting the enclosure alone.
and an M6 screw (included) to connect the frame of the enclosure
A
4
A
EARTH
GROUND