Interpretation of the results:
D AR
< 1,25
< 1,6
> 1,6
n The PRINT secondary function is described in § 6.3 ( Printing of measured values ).
4.2
DISPLAY / GRAPH KEY
n Fonction première DISPLAY
This key is used to browse through the various accessible screens containing all information available
before, during or after the measurement.
The screens vary depending to the mode selected before the measurement is started.
§
MANUAL STOP mode
Before the measurement
Information accessible :
F irst screen
D C test v oltage
A C / D C input v oltage
F requency
R esidual current
D ate, tim e
During the measurement
P I
C o nd ition o f
in sulatio n
< 1
P oor or ev en
< 2
dangerou s
< 4
G ood
> 4
E xcellent
P ress on D IS P LA Y
A C / D C input v oltage
F requency
R esidual current
V oltage bargraph
60