Descargar Imprimir esta página

Samsung DVEG45R6300 Serie Manual De Instrucciones página 20

Ocultar thumbs Ver también para DVEG45R6300 Serie:

Publicidad

Idiomas disponibles

Idiomas disponibles

Installation requirements
Ducting requirements
Weather hood type
No. of 90° elbows
0
1
2
3
NOTE
* Use a 4-inch (10.2 cm) diameter rigid aluminum or galvanized steel duct.
If you integrate the dryer's vent system with an existing exhaust system:
• Make sure the exhaust system meets all applicable local, state, and national regulations.
• Verify you are not using flexible plastic duct.
• Make sure to check for and remove all lint buildup from inside the existing ducts.
• Confirm the duct is not kinked or crushed.
• Make sure the exhaust hood damper opens and closes freely.
Manometer measurements
The static pressure in any exhaust system must not exceed 0.83 inches of water column or be less than 0.
Note that these values are measured with the dryer running with a manometer presented to the exhaust
duct that connects to the dryer. The dryer tumbler must be empty and lint filter clean.
20
English
Untitled-1 20
Recommended
4" (10.2 cm)
Rigid
80 ft. (24.4 m)
68 ft. (20.7 m)
57 ft. (17.4 m)
47 ft. (14.3 m)
Use only for short-run
installation
2.5" (6.4 cm)
Rigid
74 ft. (22.6 m)
62 ft. (18.9 m)
51 ft. (15.5 m)
41 ft. (12.5 m)
2022-09-05
10:28:37

Publicidad

loading

Este manual también es adecuado para:

Dveg45r6100 serieDve45r6300 serieDve45r6100 serieDve45r6100v