7 Electrical installation
6.2
To determine the additional
refrigerant amount
For ARXM71R
If the total liquid
piping length is...
≤10 m
Do NOT add additional refrigerant.
>10 m
R=(total length (m) of liquid
piping⁠ – ⁠ 1 0 m)×0.035
R=Additional charge (kg) (rounded in units
of 0.01 kg)
For other outdoor units
If the total liquid
piping length is...
≤10 m
Do NOT add additional refrigerant.
>10 m
R=(total length (m) of liquid
piping⁠ – ⁠ 1 0 m)×0.020
R=Additional charge (kg) (rounded in units
of 0.01 kg)
INFORMATION
Piping length is the one-way length of liquid piping.
6.3
To determine the complete
recharge amount
INFORMATION
If a complete recharge is necessary, the total refrigerant
charge is: the factory refrigerant charge (see unit name
plate) + the determined additional amount.
6.4
To charge additional refrigerant
WARNING
▪ Only use R32 as refrigerant. Other substances may
cause explosions and accidents.
▪ R32 contains fluorinated greenhouse gases. Its global
warming potential (GWP) value is 675. Do NOT vent
these gases into the atmosphere.
▪ When charging refrigerant, ALWAYS use protective
gloves and safety glasses.
Prerequisite: Before charging refrigerant, make sure the refrigerant
piping is connected and checked (leak test and vacuum drying).
1 Connect the refrigerant cylinder to the service port.
2 Charge the additional refrigerant amount.
3 Open the gas stop valve.
6.5
To fix the fluorinated greenhouse
gases label
1 Fill in the label as follows:
Contains fluorinated greenhouse gases
RXXX
kg
1
=
f
GWP: XXX
kg
2
=
2
1
kg
+
1
2
=
GWP × kg
=
tCO
1000
a
If a multilingual fluorinated greenhouse gases label is
delivered with the unit (see accessories), peel off the
applicable language and stick it on top of a.
b
Factory refrigerant charge: see unit name plate
c
Additional refrigerant amount charged
d
Total refrigerant charge
e
Quantity of fluorinated greenhouse gases of the total
refrigerant charge expressed as tonnes CO
f
GWP = Global warming potential
Installation manual
10
Then...
7
Then...
a
b
c
d
e
eq
2
equivalent.
2
NOTICE
Applicable legislation on fluorinated greenhouse gases
requires that the refrigerant charge of the unit is indicated
both in weight and CO
equivalent.
2
Formula to calculate the quantity in CO
tonnes: GWP value of the refrigerant × total refrigerant
charge [in kg] / 1000
Use the GWP value mentioned on the refrigerant charge
label.
2 Fix the label on the inside of the outdoor unit near the gas and
liquid stop valves.
Electrical installation
DANGER: RISK OF ELECTROCUTION
WARNING
▪ All wiring MUST be performed by an authorised
electrician and MUST comply with the applicable
legislation.
▪ Make electrical connections to the fixed wiring.
▪ All components procured on-site and all electrical
construction
MUST
comply
legislation.
WARNING
Appliance MUST be installed in accordance with national
wiring regulations.
WARNING
ALWAYS use multicore cable for power supply cables.
WARNING
Use an all-pole disconnection type breaker with at least
3  mm between the contact point gaps that provide full
disconnection under overvoltage category III.
WARNING
If the supply cord is damaged, it MUST be replaced by the
manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
WARNING
Do NOT connect the power supply to the indoor unit. This
could result in electrical shock or fire.
WARNING
▪ Do NOT use locally purchased electrical parts inside
the product.
▪ Do NOT branch the power supply for the drain pump,
etc. from the terminal block. This could result in
electrical shock or fire.
WARNING
Keep the interconnection wiring away from copper pipes
without thermal insulation as such pipes will be very hot.
DANGER: RISK OF ELECTROCUTION
All electrical parts (including thermistors) are powered by
the power supply. Do NOT touch them with bare hands.
equivalent
2
with
the
applicable
RXF50~71D5V1B
R32 split series
3P645642-2E – 2021.10

Publicidad

loading

Este manual también es adecuado para:

Rxf50d5v1bRxf71d5v1b