Quick Start Guide
TS700...
(production date from 2310)
Other documents
Besides this document, the following material can be found on the Internet at www.turck.com:
■
Data sheet
■
Instructions for use
■
IO-Link parameters
■
Declarations of conformity
■
Approvals
For your safety
Intended use
The compact temperature sensors of the TS700... product series are designed for measuring
temperatures in machines and plants.
The devices must only be used as described in these instructions. Any other use is not in ac-
cordance with the intended use. Turck accepts no liability for any resulting damage.
General safety instructions
■
The device meets the EMC requirements for industrial areas. When used in residential areas,
take measures to prevent radio interference.
■
Do not use the device for the protection of persons or machines.
■
The device must only be mounted, installed, operated, parameterized and maintained by
trained and qualified personnel.
■
Only operate the device within the limits stated in the technical specifications.
Product description
NOTE
These instructions apply to temperature and processing units in the TS700... product
series from production date 2310 (date format YYWW) with Smart Sensor Profile 4.1.1.
The production date can be found on the rear of the housing (see fig. 2). Devices prior to
the production date 2310 are not compatible with the Smart Sensor Profile.
For old devices, instructions document 100003050 applies.
Device overview
See fig. 1: Front view, fig. 3: Dimensions
Functions and operating modes
Type
Output
TS...LI2UPN...
Two switching outputs (PNP/NPN/Auto) according to Smart Sensor Profile
4.1.1 or one switching output (PNP/NPN/Auto) according to Smart Sensor
Profile 4.1.1 and one analog output (I/U/Auto)
TS...2UPN...
Two switching outputs (PNP/NPN/Auto) according to Smart Sensor Profile
4.1.1
The sensors can be operated in normal operation (factory settings) or in legacy mode. In nor-
mal operation, a single point mode (SPM), two point mode (TPM) or window mode (WIn) can
be set for the switching outputs. In single point mode, a limit value is set at which the selected
switching output changes its switching state. In two point mode, a lower and an upper limit are
set at which the selected switching output changes its switching state as the temperature rises
or falls.
In window mode, a lower and an upper window limit are set. Outside the window, the selected
switching output changes its switching state.
In legacy mode, a window function or a hysteresis function can be defined for the switching
outputs.
The output range of the analog output is freely scalable to the measuring range. The measured
temperature can be displayed in °C, °F or K or the resistance can be displayed in Ω.
The device parameters can be set via IO-Link and with the touchpads.
Technical data
Temperature measuring range
-50...+150 °C
Temperature of medium
-50...+150 °C
Probe length
See data sheet
Compressive strength of the probe
100 bar
Outputs
TS...LI2UPN...
Two switching outputs (PNP/NPN/Auto) or
one switching output (PNP/NPN/Auto) and
one analog output (I/U/Auto)
TS...2UPN...
Two switching outputs (PNP/NPN/Auto)
Ambient temperature
-40...+80 °C
Operating voltage
17...33 VDC
Power consumption
< 3 W
Output function
NC/NO programmable, PNP/NPN
Output 1
Switching output or IO-Link
Output 2
Switching output or analog output
Rated power
0.2 A
Degree of protection
IP67/IP69K acc. to ISO 20653
Electromagnetic compatibility (EMC)
EN 61326-2-3:2013
Shock resistance
50 g (11 ms), EN 60068-2-27
Vibration resistance
20 g (10...3000 Hz), EN 60068-2-6
Hans Turck GmbH & Co. KG | Witzlebenstraße 7, 45472 Mülheim an der Ruhr, Germany | Tel. +49 208 4952-0 | Fax +49 208 4952-264 | more@turck.com | www.turck.com
Installing
The compact temperature sensors may be mounted in any orientation. The display can be
rotated 180° (see fig. 3 and parameter DiSr).
TS700... compact temperature sensors can only be mounted with screw-in adapters from
f
the FAA-... product series.
Position one of the two seals (included in the delivery) between the screw-in adapter and
f
the process connection (e.g. union).
Screw the screw-in adapter with the seal onto the process connection (maximum torque of
f
100 Nm).
Guide the probe rod through the screw-in adapter and hand-tighten the sensor (M18 × 1.5
f
coupling nut) with the screw-in adapter.
Screw an M18 × 1.5 coupling nut onto the screw-in adapter (maximum torque of 40 Nm).
f
Optional: Rotate the sensor head within the 340° range to align the connection to the I/O
f
level as well as to ensure optimum operability and readability.
f
After removing and reinstalling the screw-in adapter, use a new seal (replacement seal
included in the delivery).
Connection
Connect the device as shown in "Wiring diagrams."
f
Commissioning
The device is operational automatically once the power supply is switched on. The auto detect
function enables the device to automatically support the pre-defined switching output be-
havior (PNP/NPN) or analog output characteristic when connected to an I/O module. The auto
detect function is activated by default.
Replacing the devices
If replacing an old device (production date prior to 2310) with a new device, proceed as follows:
Set the compatible device mode in the IO-Link master so that the device changes to Legacy
f
Mode.
Alternatively, set the Legacy Mode in the Extended Functions menu.
f
Operation
LEDs — operation
LED
Indication
Meaning
PWR
Green
Device is operational
Green flashing
IO-Link communication
FLT
Red
Error
°C
Green
Temperature in °C
°F
Green
Temperature in °F
K
Green
Temperature in K
Ω
Green
Resistance in Ω
LOC
Yellow
Device locked
Yellow flashing
"Lock/unlock" process active
Off
Device unlocked
I and II
Yellow
Switching output
(switch-
NO: Switching point exceeded/within window
–
ing point
(active output)
LEDs)
–
NC: Switching point undershot/outside window
(active output)
Off
Switching output
NO: Switching point undershot/outside window
–
(inactive output)
NC: Switching point exceeded/within window
–
(inactive output)
Display indications
Display
Meaning
- - - -
Sensor failure
HW
Internal hardware error
SC 1
Short circuit at output 1
SC 2
Short circuit at output 2
SC12
Short circuit at both outputs
WB 2
Wire break at current output 2
VOLT
Operating voltage outside the permissible range
LOAD
Burden at the analog output outside of the permissible range
Oor+
Value outside the measuring range, temperature > 5 % of full scale above the
measuring range
Oor-
Value outside the measuring range, temperature > 5 % of full scale below the
measuring range
Oor
No measurement data available
TEMP
Device temperature outside the permissible range
Err
Unspecified error
Setting and parameterization
To set the parameters via the touchpads, refer to the enclosed parameter setting instructions.
For example, parameter setting via IO-Link is explained in the IO-Link commissioning manual.
Repair
The device must not be repaired by the user. The device must be decommissioned if it is faulty.
Observe our return acceptance conditions when returning the device to Turck.
Disposal
The devices must be disposed of properly and do not belong in the domestic waste.
Wiring diagrams
TS...LI2UPN
1
2
+
2
out 2: switch / analog
3
1
4
out 1: switch / IO-Link
4
3
–
TS...2UPN...
1
2
+
2
out 2: switch
3
1
4
out 1: switch/IO-Link
4
3
–