Installation
Packaging
Crates are constructed from 3/4" (19) OSB .
Crate dimensions approx: 44" x 28" x 12" (1118 x 711 x 305)
Crates should not be stacked more than 2 high .
All crates must be stacked evenly and horizontally .
Safety issues related to packaging:
• Product should be transported with the care associated to packages labeled "FRAGILE" even if packaging
is not marked accordingly .
• Standard safety procedures for forklift transport and large items less than 1000 lb (454 kg) should be followed at all
times .
• When stored, crate must be supported in entirety of its length and width .
1
Mounting Heater
WARNING HIGH VOLTAGE SHOCK. Disconnect power supply before performing any work inside
the heater enclosure.
Installation should be performed by a qualified plumber or electrician.
If heater is installed where freezing can occur, specify Bradley's ENHT Freeze Protection option. Bradley's
ENHT option must be purchased at the time of order. Do not install in areas where freezing can occur
without the ENHT option listed in the model number.
For best results, install heater as close as possible to the point of use.
Long pipe runs are not recommended. A heat loss of 1°F for every 10 ft (3 meters) of uninsulated
pipe can occur.
When determining a mounting location, give consideration to the location of the main electrical panel
and ensure accessibility of the cabinet enclosure door and other plumbing for service/maintenance.
36" (914 mm) minimum in front of the cabinet enclosure is required.
A
Set heater in a vertical, upright position
with the water outlet located at top .
Standard Wall Mount
Mount heater to the wall using the (4)
mounting brackets on the back of the
enclosure . Bolt the heater to the vertical
B
surface . Vertical surface must support
150 pounds or more .
Optional Leg Kit
Use the floor mounting template on the
side of the crate to help with alignment .
Secure heater by bolting each leg to the
floor using 3/8" (10 mm) anchor bolts .
Install the pressure and temperature relief
C
valve on hot water outlet immediately
following the union .
NOTICE! Valve must empty into a drain.
Rectangle outlines on template is not
actual size of heater.
Template may require cutting to fit into
tight areas.
Holes are for alignment purposes and may
not represent actual drill size for mounting
hardware.
Bradley • 215-1822 Rev. D
8"
4"
(203)
(102)
1/10/2022
CLE Series Tankless Heater
20" (508)
12¼" (311)
6¼" (159)
⁷⁄₁₆" x ¾"
(10 x 20) Slot
(6 Places)
(mm)
4"
(102)
5