EN
Function
- Siemens LGB22 control and safety unit
The Siemens control box starts the fan and begins the pre-purging of the combustion chamber. The air pressure switch controls the
correct operation. At the end of the pre-purging phase, the ignition transformer cuts-in followed by the opening of the gas valves. In case
of missed ignition or accidental shutdown, the ionisation probe cuts-in and set the burner in lockout mode within the safety time.
Gas pressure swi ch
Air pressure swi ch
High flame ON/OFF
Flame de ec ion
Lock ou
!
Always disconnect the power supply before installing or removing the control unit Do not attempt to open or carry out repairs on
the control unit.
8
www.ecoflam-burners.com
2
Mo or
1
Transformer
Gas valve
lamp
3
4
Description
1
pressure swi ch con rol ime-ou
2
ime-ou for air pressure confirma ion
5
3
prewashing ime
4
safe y ime
6
5
preigni ion ime
6
ime-ou
9"
3"
30"
3"
3"
o enable fuel 2nd valve
8"