6.1
Troubleshooting table
/i
Fault
The heater does not
start up.
The heater triggers a
fault; the red lamp on
the operating panel
lights up.
20
Cause
1
The heater has no volt-
age.
2
The fan motor runs
heavily or is blocked.
3
The thermostat is set to
a too low temperature.
4
There is no through-
connector on the ther-
mostat connection.
5
Defect in the operating
panel
6
If the orange lamp also
lights, the plug is incor-
rectly inserted in the
socket.
7
There is no or not
enough gas pressure on
the gas regulator block.
8
The gas regulator block
does not open.
9
The ionisation electrode
is dirty.
40.020.955 - rev. 05 - 2017
Solution
Check the electrical connec-
tion.
Check if the fan motor is dirty
or blocked.
Replace the fan motor.
Correct the settings.
Fit the through-connector.
Repair or replace the operat-
ing panel
Reverse the plug.
Check whether the gas cock
is open.
Check the functioning of the
minimum gas pressure pro-
tection.
Check the electrical connec-
tion.
Check the gas regulator
block.
Clean the ionisation elec-
trode with steel wool.
Action
User
User
Dealer
User
User
Dealer
User
User
Dealer
User
Dealer
User
AGA 111