Descargar Imprimir esta página

Lamborghini Caloreclima ECO 3 R Manual Para La Installación Y El Mantenimiento página 22

Ocultar thumbs Ver también para ECO 3 R:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

By pressing it for more than 3 seconds, the diagnosis stage will be activated (red light flashes rapidly).
Thetable below describes the causes of the lock out or fault in relation to the number of flashes (al-
ways red).The diagnosis function is interrupted by pressing the release button for at least 3 seconds.
Visual indication
2 flashes
3 flashes
4 flashes
¬¬¬¬¬
5 flashes
¬¬¬¬¬¬
6 flashes
¬¬¬¬¬¬¬
7 flashes
8 flashes
9 flashes
10 flashes
MAIN COMPONENTS
INDEX
1 Components Plate
2 Electromagnetic Valve
3 Connection Flange
4 Photoresistance
5 Release Button
6 Electrodes set
7 Nozzle Line
(with Preheater Mod. R)
8 Automatic air flap
9 Control box
10 Pump
11 Motor
12 Body
13 Fan
14 Deflector
GB
15 Transformer
16 Draught tube
22
DIAGNOSIS OF LMO EQUIPMENT FAULTS AND LOCK OUT
Description of operating anomalies
¬¬
¬¬¬
¬¬¬¬
¬¬¬¬¬¬¬¬
¬¬¬¬¬¬¬¬¬
¬¬¬¬¬¬¬¬¬¬
Possible causes
No flame signal
- Faulty fuel valves
- Faulty flame detector
- Incorrect burner setting, no fuel
- No ignition
Not used
Stray light on ignition
Not used
Not used
No flame signal during operation
- Faulty fuel valves
- Faulty flame detector
- Incorrect burner setting, no fuel
Anomalies in fuel preheating time
Not used
Incorrect electrical connection or damage to equipment

Publicidad

loading

Este manual también es adecuado para:

Eco 3