CS10.242, CS10.242-C1 Installation Manual
EN
Product Description
The CS10.242 is a DIN-rail mountable single-phase-input power supply, which provides a floating,
stabilized and galvanically separated SELV/PELV output voltage.
The CS10.242-C1 device is the same as the CS10.242 but with conformal coated pc-boards.
Intended Use
This device is designed for installation in an enclosure and is intended for commercial use, such as in
industrial control, process control, monitoring, measurement equipment or the like.
Do not use this device in equipment, where malfunctioning may cause severe personal injury or
threaten human life without additional appropriate safety devices, that are suited for the end-
application.
If this device is used in a manner outside of its specification, the protection provided by the device may
be impaired.
Installation Instructions
Install device in an enclosure providing protection against electrical, mechanical and fire hazards.
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the bottom of the
device. Other mounting orientations require a reduction in output current.
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper
cables that are designed for a minimum operating temperature of 60°C for ambient temperatures up to
+45°C, 75°C for ambient temperatures up to +60°C and 90°C for ambient temperatures up to +70°C.
Ensure that all strands of a stranded wire enter the terminal connection. Use ferrules for wires on the
input terminals. Unused screw terminals should be securely tightened.
The device is designed for pollution degree 2 areas in controlled environments. No condensation or
frost is allowed.
The enclosure of the device provides a degree of protection of IP20. The housing does not provide
protection against spilled liquids.
The device is designed for overvoltage category II zones. Below 2000m altitude the device is tested
for impulse withstand voltages up to 4kV, which corresponds to OVC III according to IEC 60664-1.
The device is designed as "Class of Protection I" equipment according to IEC 61140. Do not use
without a proper PE (Protective Earth) connection.
The device is suitable to be supplied from TN, TT and IT mains networks. The continuous voltage
between the input terminals and the PE potential must not exceed 300Vac.
A disconnecting means shall be provided for the input of the device.
The device is designed for convection cooling and does not require an external fan. Do not obstruct
airflow and do not cover ventilation grid!
The device is designed for altitudes up to 5000m (16400ft). Above 2000m (6560ft) a reduction in
output current is required.
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and
right side. Increase the 5mm to 15mm in case the adjacent device is a heat source. When the device
is permanently loaded with less than 50%, the 5mm can be reduced to zero.
The device is designed, tested and approved for branch circuits up to 20A without additional protection
device. If an external fuse is utilized, do not use circuit breakers smaller than 10A B- or 6A C-
Characteristic to avoid a nuisance tripping of the circuit breaker.
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the
same as the ambient or surrounding air temperature and is defined 2cm below the device.
The device is designed to operate in areas between 5% and 95% relative humidity.
Installation Instructions for Hazardous Location Areas
The device is suitable for use in Class I Division 2 Groups A, B, C, D locations.
Substitution of components may impair suitability for this environment.
Do not disconnect the device or operate the voltage adjustment unless power has been switched off or
the area is known to be non-hazardous.
Functional Description
The output is electronically protected against no-load, overload and short circuit and can supply any
kind of loads, including inductive or capacitive loads.
Do not apply return voltages from the load to the output terminals higher than 35V.
The output voltage can be adjusted with a small flat-blade screwdriver on the front of the unit.
The green DC OK LED reports a voltage on the output terminals above 21V.
The device is equipped with an over-temperature protection. In case of a high temperature, the output
shuts down and starts automatically again after cooling off.
Do not parallel devices for higher output currents.
Same devices can be connected in series for higher output voltages. It is allowed to connect as many
devices in series as needed, providing the sum of the output voltage does not exceed 150Vdc.
In case of an internal defect, a redundant circuit limits the maximum output voltage to 39V. The output
shuts down and automatically attempts to restart.
Technical Data
All values are typical figures specified at 230Vac 50Hz input voltage, 24V
10A output load, 25°C ambient temperature and after a 5 minutes run-in
time unless otherwise noted.
Output voltage
DC 24V
24 – 28Vdc
Adjustment range
12.0 – 10.3A
Output current
10.0 – 8.6A
7.5 – 6.4A
Derate linearly between +45°C and +70°C
AC 100-120V /
Input voltage AC
200-240V
50 – 60Hz
Mains frequency
Input current AC
3.73 / 2.0A
Power factor
0.59 / 0.57
Input inrush current
3 / 3A pk
Efficiency
91.0 / 91.2%
Power losses
23.7 / 23.2W
Hold-up time
46/ 42ms
-25 to +70°C
Temperature range
4mm²
Max. wire size (litz wire)
Wire size AWG
AWG 20-10
Max. wire diameter
2.8mm
Wire stripping length
7mm / 0.28inch
Tightening torque
1Nm / 9lb.inch
Size (wxhxd)
60x124x117mm
Weight
800g / 1.76lb
Functional Diagram
Output Characteristic
Temperature Range
Allowed output current at 24V
12A
10A
7.5A
A: continuous
B: short term (max. 60s)
0A
-25
0
Nominal
Factory setting 24.1V
Below +45°C ambient
At +60°C ambient
At +70°C ambient
±10%, auto select
±6%
At 120 / 230Vac
At 120 / 230Vac
At 120 / 230Vac, temp.
independent
At 120 / 230Vac
At 120 / 230Vac
At 120 / 230Va
Without DIN-rail
OUT
B
A
+45
+60
+70°C
Ambient temperature