Descargar Imprimir esta página

Orbis DATA LOG BT Manual De Instrucciones página 4

Publicidad

Idiomas disponibles

Idiomas disponibles

SETTINGS
CLOCK
✓
PROGRAMS. This is the menu where the different operations are programmed. There are 40 memory spaces
(P-01 to P-40).
 ENTER. We enter by pressing ✓, and with the ▼ and ▲ keys we move through the different programs
stored in the memory.
When entering this menu, if any programs have already been stored, the first program that was stored
appears in the display text line: "P-01", and with the ▲ key we can go up the different stored programs until
we reach the first empty program, in which the display text line will show "P-XX EMPTY" alternating with the
number of programs available left in the memory of the device.
When entering this menu, if no other programs have been created, the display text line will show: "P-01
EMPTY" alternating with "40 LEFT" referring to the memory spaces available.
If we wish to modify or create a program we move to it with the ▼ and ▲ keys, and press ✓. Next, with the
▼ and ▲ keys we select one of the following options:
o EDIT. This option allows us to choose the type of operation that will be performed in the selected
program. By pressing ✓, "ON TYPE" will be displayed and with the ▼ and ▲ keys we can choose the
type of operation. The operations can be:
- ON TYPE. Switch-on of the connected circuit at a fixed time.
- OFF TYPE. Switch-off of the connected circuit at a fixed time.
- CYCLE TYPE. ON and OFF operations performed repeatedly from beginning to end. To program the
beginning of the cycle we have to indicate the hour, minutes, and days of the week when this cycle
will begin. Next, we need to specify the respective ON and OFF duration (in hours, minutes or in
seconds). To finish, we must indicate the hour, minutes, and days of the week when this cycle will
stop operating.
- PULSE TYPE. Switch-on of the circuit in a pulse of a set duration at a fixed time of the day.
Once the type of operation has been chosen, we have to select the cannel or channels it affects (C1, C2
or C1 + C2).
Next, we enter the operation starting hours and the rest of the necessary times according to the selected
operation.
HOLIDAY PERIODS program
If when validating the last day of the week with the ✓ key we keep it pressed, we select this operation as
holiday. The word HOLIDAY is displayed and with the ▼ and ▲ keys we select one of the 4 holiday
periods.
o DELETE. By pressing ✓, the selected program is deleted. Since all programs are stored consecutively,
deleting one program can change the number assigned to each one of them.
 DELETE. This option allows for deleting all the operations of the last 40 programs in just one step.
We choose to perform the switch-on program at 10 pm
MENU
PROGRAMS
Hour and
CHANNEL
min
C1 and C2
22:00
We choose to perform the switch-off program at 12 am
MENU
PROGRAMS
Hour and
CHANNEL
min
C1 and C2
00:00
We choose to perform the cycle program, with a 5-second ON and a 10-second OFF period, which will
start at 6:00 and will finish at 8:00 during the entire week
MENU
PROGRAMS
FROM
CHANNEL
Hour and
min.
C1 y C2
06:00
OFF TIME
Hour and
SECONDS
min.
00:00
10
We choose to perform the pulse program, which will perform a 5-second ON period starting at 11:30
during the entire week
MENU
PROGRAMS
Hour and
CHANNEL
min.
C1 and C2
11:30
LANGUAGE
ADVANCED
BRIGHTNESS
PERMANENT
HOLIDAYS
METERS
SEASON
PIN CODE
12 H / 24 H
VERSION
ENTER
P01
EDIT
Days of the
week
Mon...Sun
P01 OK
ENTER
P02
EDIT
Days of the
week
Mon...Sun
P02 OK
ENTER
P03
EDIT
ON TIME
Days of the
Hour and
SECONDS
week
min.
Mon...Sun
00:00
UNTIL
Days of the
Hour and
week
min.
08:00
Mon...Sun
ENTER
P04
EDIT
Days of the
SECONDS
week
05
Mon...Sun
SETTINGS. This is the menu where we configure the device.
 CLOCK. Sets the time of the device. The variables to configure are (in this order): Year, month, day, hour
✓
and minute. The day of the week is calculated automatically.
 LANGUAGE. This is the menu where the language of the device is selected.
 ADVANCED. This is the menu where most of the device configuration can be done.
o BRIGHTNESS. Menu where we can select the brightness of the display. MINIMUM, LOW, MEDIUM,
HIGH, or MAXIMUM. The brightness on screen will be adjusted if we validate the visualised level.
o PERMANENT. The menu where we can set a permanent operation (ON or OFF) of channel C1 and
channel C2. With the ▼ and ▲keys we move through the different options: C1: YES  C1: NO  C2:
YES  C2: NO. We validate with 3 our desired option. The device will not take notice of the operation
programming for the selected channel if we choose the YES OPTION.
o The contact position can be changed manually (see MANUAL OPERATION)
o HOLIDAYS. It has 4 PERIODS that can be programmed to perform the operations selected in the
programming of HOLIDAY PERIODS. If no operation is programmed in a period, the channels will
remain OFF during said period. PERIOD 1 ...4
- EDIT. The month, day, hour and minute of the beginning of the period and the month, day, hour and
minute of the end of the period are programmed. This period will be repeated year after year.
- DELETE. The selected period is deleted.
o METERS. Menu where the switch-on time of each circuit is indicated (in hours). Accessing the meter of
each channel with ✓, they can be set to zero. Select DELETE YES and validate.
o SEASON. Allows for adjusting the time change from daylight saving to standard time and vice versa.
- ACTIVE. Automatically makes the time change from daylight saving to standard time or vice versa, in
accordance with each country's legislation. (EU the last Sunday of March and the last Sunday of
October)
- INACTIVE. Does not make the time change.
o PIN CODE. Menu to activate or disable the keyboard lock to prevent unwanted access to the device
settings.
- INACTIVE. Keyboard lock disabled.
- ACTIVE. Keyboard lock activated. And we are required to program a four-figure PIN CODE. This
protection will be activated 30 seconds after we come out of the settings and return to the display in
standby mode. From that moment on when any key is pressed the message "PIN CODE" will appear
on screen. To unblock the access to the device, we will need to enter the PIN CODE programmed in
its activation. The device will be unblocked for 10 seconds. During this time we will be able to access
the settings menu by pressing 3. After 30 seconds without handling the device, it will get locked again.
o 12H – 24H. With the ▼ and ▲keys we select the mode in which we wish to see the time. We validate
the selection with ✓
o VERSION. Menu where the software version of the device is shown.
If simultaneous operations are programmed we have to take into account that some have priority over the
others. The priority order is as follows:
RESET. SET TO ZERO.
Starting on standby mode (main screen), press the C key and while keeping it pressed press the ▼ and ▲
keys simultaneously for more than 3 seconds. The display gets turned off, all programming is deleted. The
device must be powered.
We can also perform a quick deletion that does not affect the programming by pressing the four keys
simultaneously. The device must be powered.
BATTERY CHANGE. FIG. 4
The device has a power-reserve of 4 years, by means of a replaceable CR2032 lithium battery. Battery
replacement is made by removing the battery holder placed on the front of the device through a flat-head
screwdriver. Observe the battery polarity as marked on the battery holder.
When the battery is dead and the device is powered the battery symbol appears on screen.
NOTE: When changing the battery the device's programming is not lost, and neither is the current time.
TURN OFF THE POWER SUPPLY TO REPLACE THE BATTERY
PROGRAMMING VIA SMARTPHONE/TABLET
It incorporates a bluetooth system 4.0 LE for the communication with an application installed on a portable
smart device (Apple or Android) Bluetooth Smart Ready compatible.
- Apple (iPhone 4S or higher, IPad 3 or higher)
- Android (version 4.3 or higher and device compatible with Bluetooth 4.0 LE)
To communicate with Data Log or Data Log 2 is needed to have the application ORBIS DATA LOG installed.
This App allows the following functions:
TYPE
 To read the data of a device to store them or to send them to another device
 To create different profiles (configurations) from beginning or from an already existing profile of other device
ON
 To send a profile to one or several device
 To see performance statistics (monthly and yearly number of ON-hours).
To start using the App follows the next steps:
1. Download the App from AppStore or PlayStore, making sure your device is compatible with technology
Bluetooth Smart Ready.
2. Start the App and select the option "Connect with the device"
device.
3. Check and/or modify the received data and store
TYPE
modified profile to the device
OFF
4. Close the App and disconnect the bluetooth from device for a normal function of the device.
TECHNICAL FEATURES
Rated voltage and frequency
Resistance
Breaking capacity:
Maximum recommended loads (N.A):
Own consumption
Contact
TYPE
Display screen
Running accuracy
CYCLE
Accuracy variation with temperature
Power reserve
Type of action
Software class and structure
Memory spaces
05
No. of channels
Types of operations
Astronomical adjustments
Operating temperature
Transport and storage temperature
P03 OK
Pollution situation
Protection level
Protection class
Transient impulse voltage
Temperature for the ball test
Keyboard access cover
TYPE
Connection
PULSE
Battery
Wrapping size
WARNING:
This time switch includes a battery whose contents may be damaging to the environment. Do not get rid of the
P04 OK
product without taking the precaution of dismantling the battery and placing it in an appropriate recycling
container, or sending the product back to the factory.
Hereby, ORBIS TECNOLOGÍA ELÉCTRICA, S.A. declares that the radio equipment type DATA LOG BT /
DATA LOG 2 BT is in compliance with Directive 2014/53/EU. The full text of the EU declaration of conformity
is available at the following internet address: http://www.orbis.es/downloads/declarations-of-conformity
PERMANENT MODE  MANUAL  PROG_01  PROG_02  ....  PROG_40
.
As indicated in the device
± 10%
DATA LOG BT: µ 16 (10) A / 250 V~
DATA LOG 2 BT: µ 2x16 (10) A / 250 V~
FIG.3
16 VA (1.3 W) maximum
AgSnO
switched.
2
Back-lit LCD
± 1 s / day at 23 ºC
± 0.15 s / ºC / 24 h
4 years (with battery and no network connection)
48 h (no battery and no network connection)
1S, 1T, 1U
Class A
40
1 channel DATA LOG BT; 2 channels DATA LOG 2 BT
ON/OFF, PULSE (1 to 59 sec.) and CYCLES (1 to 59 sec. or 1
min to 23h and 59 min).
± 1 second
-10 ºC at +45 ºC
-20 ºC at +60 ºC
2
IP20 according to EN60529
II under correct mounting conditions
2.5 kV
+ 80 ºC for 21.2.5
Sealable
With screw terminal for wire cross section of up to 4mm²
CR2032 – 3 V – 220 mAh
2 DIN modules (35 mm) FIG.5
Subject to technical changes – for further information: www.orbis.es
to read the data (configuration) of the
the profile for a future use and/or send again the

Publicidad

loading

Este manual también es adecuado para:

Data log 2 bt