Checks to the refrigeration equipment
Where electrical components are being changed, they shall be fit
for the purpose and to the correct specification. At all times the
manufacturer´s maintenance and service guidelines shall be
followed. If in doubt consult the manufacturer´s technical
department for assistance.
The following checks shall be applied to installations using
flammable refrigerants:
- The charge size is in accordance with the room size within which
the refrigerant containing parts are installed;
- The ventilation machinery and outlets are operating adequately
and are not obstructed;
- If an indirect refrigerating circuit is being used, the secondary
circuit shall be checked for the presence of refrigerant;
- Marking to the equipment continues to be visible and legible.
Markings and signs that are illegible shall be corrected;
- Refrigeration pipe or components are installed in a position
Where they are unlikely to be exposed to any substance which
may corrode refrigerant containing components, unless the
components are constructed of materials which are inherently
resistant to being corroded or are suitably protected against
being so corroded.
Checks to electrical devices
Repair and maintenance to electrical components shall include
initial safety checks and component inspection procedures. If a
fault exists that could compromise safety, then no electrical
supply shall be connected to the circuit until it is satisfactorily
dealt with. If the fault cannot be corrected immediately but it is
necessary to continue operation, an adequate temporary solution
shall be used. This shall be reported to the owner of the
equipment so all parties are advised.