Operation
7
The STANDBY MODE selection screen will appear.
To Advance to
the Next Screen:
Press SCROLL (
)
v
8
The FREQUENCY CONVERTER selection screen will appear.
To Advance to
the Next Screen:
Press SCROLL (
)
v
9
The ECONOMY MODE selection screen will appear.
To Advance to
the Next Screen:
Press SCROLL (
)
v
Continued on page 20.
13-11-177-9332C3.indb 19
STANDBY MODE screen allows users to enable the UPS to provide output power when
running in standby mode. The standby mode factory configuration is NO OUTPUT. In this
configuration, the screen will alternate between STANDBY MODE / PRESS ON KEY TO TURN
UPS ON.
Note: To enable bypass power output in standby mode, select BYPASS OUTPUT in the standby mode configuration
screen. In this configuration, the screen will alternate between BYPASS MODE / PRESS ON KEY TO TURN UPS ON.
To Change This
NO OUTPUT*
Setting:
Press "SELECT" ( ^ )
SCROLL
Note: The UPS must be
in Standby Mode to
change this setting.
FREQUENCY CONVERTER refers to the ability of the UPS to convert 60Hz to 50Hz or 50Hz to
60Hz. The UPS system automatically selects 50 Hz or 60 Hz operation based on utility
power conditions at start-up. The factory configuration of DISABLE is ideal for most
applications. Some users may wish to convert frequency for connected equipment. To
successfully configure your UPS for frequency conversion, ENABLE the FREQUENCY
CONVERTER function and SET the OUTPUT FREQUENCY function to the desired 50 or 60 Hz
setting.
To Change This
Setting:
Press "SELECT" ( ^ )
SCROLL
Note: The UPS must be
in Standby Mode to
change this setting.
ECONOMY MODE is a UPS setting that enables enhanced efficiency and reduced BTU output
by suspending double-conversion circuits whenever input power is already of sufficient quality
to run connected equipment. In economy mode, the UPS consults the current BYPASS
RANGE setting (+/-5% to 10%). When input voltage strays pass the selected percentage
preset, the UPS will automatically switch to on-line mode. When input voltage falls back
within bypass range settings the UPS will automatically return to economy mode. Note: The
suggested setting range is +/- 5% to +/- 10%.
To Change This
Setting:
Press "SELECT" ( ^ )
SCROLL
Press "SELECT" (^) to SET this value.
Press "SCROLL" (v) to advance to the next option.
Available values are: No output & Bypass output
SELECT
Scroll through available values and press
SELECT (^) to SET.
Factory default = NO OUTPUT
Press "SELECT" ( ^ ) to SET this value.
DISABLE*
Press "SCROLL" (
Available values are: ENABLE, DISABLE
SELECT
Scroll through available values and press
SELECT ( ^ ) to SET.
Factory default = DISABLE
Press "SELECT" ( ^ ) to SET this value.
DISABLE*
Press "SCROLL" (
SELECT
Available values are: ENABLE, DISABLE
Scroll through available values and press
SELECT ( ^ ) to SET.
Factory default = DISABLE
19
) to advance to the next option.
v
) to advance to the next option.
v
11/27/2013 4:12:59 PM