Technical features
Rated Voltage Range
Input
Rated Frequency
Rated Voltage Range
Output
Frequency Range
Carrier Frequency
Input Frequency Resolution
Control Mode
Overload Capacity
Torque Elevating
Control Mode
V/F Curve
DC Braking
Jogging Control
Auto Circulating Running
and multi-stage speed running
Built-in PID regulation
Frequency Setting
Start/Stop Control
Running Command Channels
Operation Function
Frequency Source
Accessorial frequency Source
Braking module
Serial Port
Optional
Remote keypad
Built-in EMI filter, IEC/EN 61800-3: 2004 Adjustable speed electrical power drive systems-Part 3: EMC product
EMC compliance
standard including specific test methods.
Possible causes of malfunction: input/output phase, under voltage, over voltage, overload, overheat, user password
Protection system
error, external interference.
LED shows present output frequency, present rotate-speed (rpm), present output current, present output voltage,
Display
present linear-velocity, types of faults, and parameters for the system and operation; LED indicators show the
current working status of the inverter.
Equipment Location
Environment Temperature
Environment
Conditions
Environment Humidity
Vibration Strength
Height above sea level
Protection level
IP 20
Applicable Motor
0.2kW ~ 15kW
Items
Variable frequency drive
Contents
3-phase 400V±15%; single-phase 230V±15%
50/60Hz
3-phase 0~400V;3-phase 0~230V
0.50 ~ 650.0Hz
2kHz~10kHz; Fixed carrier-wave and random carrier-wave
can be selected by F159
Digital setting: 0.01Hz, analogue setting:
0.1% max frequency
Enhanced V/Hz control
150% rated current, 60 seconds
Auto torque promotion, Manual Torque Promotion
0.1%~30.0% (V/Hz)
4 kinds of modes: linear type, square type, under-defined V/Hz
curve and auto torque compensation
DC braking frequency: 1.0~5.0 Hz, braking time: 0.0~10.0s
Jogging frequency range: min frequency~ max frequency,
jogging acceleration / deceleration time: 0.1~3000.0s
Auto circulating running or terminals control
allow 15-stage speed running.
Easy to create a system for closed-loop control
Potentiometer or external analogue signal (0~5V, 0~10V, 0~20mA);
keypad (terminal)▲/▼ keys, external control logic and automatic
circulation setting.
Terminal control, keypad control or communication control.
3 kinds of channels from keypad panel, control terminal and serial
communication port.
Frequency sources: keypad, analogue voltage signal, analogue current
signal and serial communication port.
Flexible implementation of 5 kinds of accessorial frequency fine
adjustments and frequency compound.
Built-in braking module (only three phase 400 Vac)
Modbus communication
In an indoor location, Prevent exposure from direct sunlight, free from
dust, flammable gases, steam or salt contained substances, etc.
-10°C ~ + 50°C
Below 90% (without moisture)
Below 0.5g (acceleration)
1000m or below
TT100
13