  • MEXICANO, página 59
Protection classes for module
Degrees of protection (IEC/EN
60529)
Enclosure types (UL 50/50E)
Overvoltage category
(IEC/EN 60664-1)
Protective class (IEC/EN 61800-
5-1)
Ambient conditions
Installation altitude
Surrounding air
temperature
Markings
The applicable markings are shown on the type designation label of the drive.
CE
UL
Heatsink: IP55
UL Open Type
Heatsink: UL Type 12
III
I
For TN and TT neutral-grounded network systems and IT non-cornergrounded
network systems: 0 to 4000 m (13123 ft) above sea level
For corner-grounded network systems: 0 to 2000 m (6561 ft) above sea level
Installation on 525...690 V corner-grounded or midpoint-grounded delta
systems is not permitted.
The output current must be derated by 1% for each 100 m (328 ft) at altitudes
above 1000 m (3281 ft).
Operation: -15 ...+55 °C (5...131 °F). Frost is not permitted. The rated output
current must be derated by 1% for each 1 °C (1.8 °F) over 40 °C (104 °F).
Storage in the package: -40 to +70 °C (-40 to +158 °F).