WIKA LSD-30 Manual De Instrucciones página 22

Interruptor de nivel
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

6. Commissioning, operation
6.4 Switching functions
Hysteresis function
GB
If the level fluctuates around the set point, the hysteresis keeps
the switching status of the outputs stable. With increasing level,
the output switches when reaching the switch point (SP).
Contact normally open (HNO): active
Contact normally closed (HNC): inactive
With the level falling again, the output will not switch back before
the reset point (RP) is reached.
Contact normally open (HNO): inactive
Contact normally closed (HNC): active
Window function
The window function allows for the control of a defined range.
When the level is between window High (FH) and window Low
(FL), the output switches on.
Contact normally open (FNO): active
Contact normally closed (FNC): inactive
When the level is outside window High (FH) and window Low
(FL), the output does not switch on.
Contact normally open (FNO): inactive
Contact normally closed (FNC): active
22
WIKA operating instructions level switch model LSD-30
Fig.: Hysteresis function
Fig.: Window function

Publicidad

Tabla de contenido
loading

Tabla de contenido