9. Test run
Refer to the following tables for details on the check codes. (Wireless remote controller)
[ Output pattern A]
Beeper sounds
Beep
OPERATION
INDICATOR
Off
lamp blinking
Approx. 2.5 sec.
pattern
Self-check starts
(Start signal
received)
[ Output pattern B]
Beep
Beeper sounds
OPERATION
INDICATOR
Off
lamp blinking
pattern
Approx. 2.5 sec.
Self-check starts
(Start signal
received)
[ Output pattern A] Errors detected by indoor unit
Wireless remote controller
Beeper sounds/OPERATION
INDICATOR lamp flashes
(Number of times)
1
2
3
4
5
6
7
8
9
10
11
12
14
No sound
[ Output pattern B] Errors detected by unit other than indoor unit (outdoor unit, etc.)
Wireless remote controller
Beeper sounds/OPERATION
INDICATOR
lamp flashes (Number of times)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
*1 If the beeper does not sound again after the initial t o beeps to confirm the self-check start signal
not come on, there are no error records.
*2 If the beeper sounds three times continuously "beep, beep, beep (0.4 + 0.4 + 0.4 sec.)" after the initial t o beeps to confirm the self-check start signal
received, the specified refrigerant address is incorrect.
• On wireless remote controller
The continuous buzzer sounds from receiving section of indoor unit.
Blink of operation lamp
Beep
Beep
Beep
Beep
th
1
st
2
nd
3
rd
n
On
On
On
On
0.5 sec.
0.5 sec.
0.5 sec.
0.5 sec.
Number of blinks/beeps in pattern indicates the
check code in the following table (i.e., n= 5 for "P5")
Beep
Beep
1
st
2
nd
On
On
On
0.5 sec.
0.5 sec.
Approx.3 sec.
Number of blinks/beeps in pattern indicates the
check code in the following table (i.e., n = 5 for "U2")
Wired remote
controller
Check code
P1
Intake sensor error
P2, P9
Pipe (Liquid or 2-phase pipe) sensor error
E6, E7
Indoor/outdoor unit communication error
P4
Drain sensor error
P5
Drain pump error
P6
Freezing/Overheating safeguard operation
EE
Communication error between indoor and outdoor units
P8
Pipe temperature error
E4
Remote controller signal receiving error
–
–
–
–
Fb
Indoor unit control system error (memory error, etc.)
PL
Refrigerant circuit abnormal
– –
No corresponding
Wired remote
controller
Check code
E9
Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit)
UP
Compressor overcurrent interruption
U3, U4
Open/short of outdoor unit thermistors
UF
Compressor overcurrent interruption (When compressor locked)
Abnormal high discharging temperature/49C worked/insufficient refrigerant
U2
U1, Ud
Abnormal high pressure (63H worked)/Overheating safeguard operation
U5
Abnormal temperature of heat sink
U8
Outdoor unit fan protection stop
U6
Compressor overcurrent interruption/Abnormal of power module
U7
Abnormality of super heat due to low discharge temperature
Abnormality such as overvoltage or voltage shortage and abnormal
U9, UH
synchronous signal to main circuit/Current sensor error
–
–
–
–
Others
Other errors (Refer to the technical manual for the outdoor unit.)
Beep
Beep
1
st
2
nd
· · · Repeated
Off
On
On
Approx. 2.5 sec.
0.5 sec.
0.5 sec.
Number of blinks/beeps in pattern indicates the
check code in the following table
Beep
Beep
n
th
3
rd
Off
On
On
0.5 sec.
0.5 sec.
Approx. 2.5 sec.
Symptom
Symptom
as received and the OPERATION INDICATOR lamp does
Beep
Beep
1
st
2
nd
· · · Repeated
On
On
On
0.5 sec.
0.5 sec.
Approx.3 sec.
Number of blinks/beeps in pattern indicates the
check code in the following table
Remark
Remark
For details, check the LED
display of the outdoor controller
board.