Descargar Imprimir esta página

AERMEC FMT21 Manual De Uso E Instalación página 8

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

We'd like to congratulate you on your purchase of the Aermec FMT21 electronic
control
panel
with
compliance
with
the
The FMT21 regulating thermostat is a control
panel for fan coils, to be assembled on the
wall.
It controls the working of the fan coil on
the basis of the mode set and the room
temperature, to maintain the desired
temperature.
The panels must be wall-mounted. They are
used on systems with 4 tubes, 2 tubes and
2 tubes with resistance, with the possibility
to connect two valves of the On-Off type for
the interception of the water to power the
batteries.
Each control panel can control a single fan
coil.
The control panel only consists of mains
voltage 220-230V ~ 50/60Hz electrical
circuits; all the inputs for the probes and
FUNCTIONS
The thermostat maintains the temperature
set for the room.
The FMT21 control panel is equipped with
the following functions:
- S e l e c t i o n o f t h e wo r k i n g m o d e
Automatic, Heating, Cooling, Ventilation
Only.
- Manual season change.
- Automatic season changeover, air side.
- Water minimum temperature control
( h e a t i n g ) a n d w a t e r m a x i m u m
temperature control (cooling) by means
of the SWA accessory, for 2-pipe systems
without resistance.
With the accessory, ventilation is
prevented if the temperature of the
system water is not suitable for the
functioning mode, thus guaranteeing
comfort and energy saving.
- manual choice of the ventilation speed;
- automatic choice of the ventilation speed
on the basis of the room temperature;
- thermostat-controlled ventilation;
- continuous ventilation;
- Ventilation only functioning mode.
- visualisation of the set temperature;
- visualisation of the set ventilation speed;
- visualisation of the Heating working
mode;
- visualisation of the Cooling working
mode;
- visualisation of the Automatic working
mode;
- start-up of the fan coil, maintaining the
settings used before the last switch-off;
- after a power failure, the fan coil restarts
keeping the the settings that were active
before the power failure;
- air temperature probe incorporated in
the panel;
- SWA external probe accessory (length
L=6m). It detects the temperature
8
thermostat.
Made
safety
standards,
controls must therefore be correspondingly
insulated for this voltage.
The valve servo commands must also be
scaled for 220-230V ~ 50/60Hz
FMT21 must only be installed by specialised
personnel.
Disconnect the power supply before
beginning any installation or maintenance
operations. Touching live components could
electrocute you.
TECHNICAL SPECIFICATIONS:
Power supply: 220-230V ~ 50/60Hz
Rated Current = 4.1A (Inductive Load)
Rated Current (Each Output) = 2A (Inductive
Load)
Adjustable temperature range: 10°C - 30°C
Differential: ±0.5°C
Environmental working conditions:
of the room air if connected to the
connector (A). The room air temperature
probe, incorporated in the panel, is
automatically disabled. t detects the
temperature of the water in the system
for ventilation consent if connected to
the connector (W). Two SWA probes
can be connected simultaneously to the
FMT21 panel.
VENTILATION
Controls the ventilation, at three speeds
which can be selected manually or
automatically.
The ventilation speed is set by means of
the thermostat button
Manual management - the fan uses the
On-Off cycles on the selected speed.
Automatic management - visualisation
, the fan speed is managed by the
microprocessor.
The automatic management of the speed is
used in the Cooling, Heating and Automatic
modes.
The minimum working time between one
speed and another is 30 seconds.
"VENTILATION ONLY" mode
The VENTILATION ONLY mode allows for
the working of the fan coil even when the
hydraulic system is switched off; in the
event that cold or hot water is circulating,
the ventilation will be continuous and not
controlled by the thermostat.
CONTINUOUS VENTILATION
The ventilation continues to work even
if the set temperature is reached, so the
temperature is therefore controlled by
means of the opening and closing of the
water valve(s) inserted in the system.
Do not use this setting in systems
without water interception valves, as the
ventilation will be continuous, and not
controlled by the thermostat.
from
high
quality
"FMT21"
is
easy
1°C - 60°C with relative humidity 10% - 90%,
without condensation.
Environmental storage conditions:
-18°C - 60°C with relative humidity 10% - 90%,
without condensation.
Material: ABS UL94 V5B
Colour: RAL 9016
Meets:
LVD 2014/35/UE:
(EN 60730-1, EN 60730-2-9)
EMCD 2014/30/UE:
(EN 55014-1, EN 55014-2)
T H E R M O S T A T - C O N T R O L L E D
VENTILATION
The ventilation switches off automatically
when the set temperature is reached.
MINIMUM/MAXIMUM water temperature
(Tw) check with SWA accessory( fo r
thermostat-controlled ventilation)
If the water is not suitable for the
functioning mode, the icon
slowly on the screen.
On
.
Tw = Water temperature
Ta = Air temperature
ALARMS:
If Tw<1°C or Tw>80°C, the icon
displayed. The thermostat continues
operating without checking the water.
If Ta<1°C or Ta>40°C, the icon
flash quickly on the screen, the thermostat
closes the valve/s and turns off ventilation.
AUTOMATIC CHANGEOVER, AIR SIDE
Function active only in AUTOMATIC mode.
The control allows to automatically establish
the functioning mode of the fan coil in
Heating or in Cooling mode depending on the
temperature set and the room temperature
detected by the air probe.
materials,
entirely
to
use
and
long-lasting.
Cooling
Heating
Off
Off
22°C
25°C
31°C
Ventilation
Ventilation
in
will flash
On
Tw°C
35°C
is
will

Publicidad